Power Meter
–
POM200
User Manual v1
www.compressedairalliance.com
41
Configure Meter
You can configure the power meter by writing command and command parameters
to corresponding command registers using Modbus function 16.
Command request
T
he following table describes a Modbus command request:
Slave
Address
(8 bits)
Function
Code
(8 bits)
Command
Register
Address
(16 bits)
Command
Register
Number
(16 bits)
Data
Length
(8 bits)
Command Register
Value
(16 bits) X N
CRC
(
1
6 bits)
1-247
16
High
8 bits
Low
8
bits
High
8
bits
Low
8
bits
N×2
Command Parameter
Low
8
bits
High
8
bits
Command Result
The command result can be obtained by reading registers 424 and 425.
The following table describes the command result:
Register
Address
Content
Size
(Int16)
Data (example)
424
Requested Command
Number
1
1001(set Date Time)
425
Result
1
0 = Valid Operation
80 = Invalid Command
81 = Invalid Parameter
82 = Invalid Number of
Parameters
83 = Operation Not Performed
Summary of Contents for POM200
Page 1: ...www compressedairalliance com 1 User Manual Power Meter Din Rail with Display Model POM200...
Page 19: ...Power Meter POM200 User Manual v1 www compressedairalliance com 19 3PH4W no VT...
Page 20: ...Power Meter POM200 User Manual v1 www compressedairalliance com 20 3PH4W with VT...
Page 21: ...Power Meter POM200 User Manual v1 www compressedairalliance com 21 3PH3W no VT 3PH3W with VT...
Page 22: ...Power Meter POM200 User Manual v1 www compressedairalliance com 22 1PH3W 1PH2W...
Page 23: ...Power Meter POM200 User Manual v1 www compressedairalliance com 23 Input Output Wiring diagram...