ELECTRICAL CONNECTIONS
CAUTION:
ELECTRICAL CONNECTIONS NEED TO BE DONE INSIDE A PROPER BRANCH BOX (not included)
CAUTION:
ALL UNCONNECTED WIRE TERMINALS MUST BE ISOLATED
MAXIMUM CABLE LENGTH 30 METERS
EXTERNAL SENSOR
(RFSONDAE)
230V / 24V
50Hz
Modbus
RTU
CABLE
5 X 0,5 mm^2
CABLE
17 X 0,5 mm^2
ROOM THERMOSTAT
SWITCH
SUMMER/WINTER
DEHUMIDIFICATION *- 24V DC
CONTROL RELAY
DEHUMIDIFIER
WITH INTEGRATION FUNCTION
POWER SUPPLY 24V DC
(AL24VDC)
POWER
SUPPLY CABLE
5 x 0,5mm^2
SIGNAL CABLE
15 x 0,5mm^2
DIGITAL OUTLETS
DIGITAL INLETS
OUTDOOR
TEMPERATURE PROBE
ANALOG INPUT
RELATIVE HUMIDITY
AMBIENT
TEMPERATURE PROBE
MIXED
TEMPERATURE PROBE
RS485
Modbus RTU
230V 50/60 Hz
24V 50/60 Hz
PUMP CONTROL
Max 250V 1A
D+. D-
PHASE
NEUTRAL
TEMPERATURE AND RELATIVE
HUMIDITY SENSOR
(RFTRUEE10)
INTEGRATION *- 24V DC
CONTROL RELAY
SUMMER/WINTER CONTROL
RELAY *- 24V DC
PUMP DRIVE RELAY
230V
SYSTEM PUMP
RFSONDAT
EARTH
BROWN
BLUE
RED
BLACK
GREEN
ORANGE
CENTRAL REGULATOR
TEMPERATURE SENSOR
* use the relay if the contacts of the connected devices are not voltage-free
Pin = pump power supply phase inlet
Pout = pump power supply phase outlet