230V • 24V 50 Hz
15 VA
14 VA
35 sec
45 sec
Compamix PR
Diamix PR
Power supply (110 V and 60 Hz on request)
Maximum power consumption
Operating time ( 90°)
Protection degree
Operational room temperature
Fluid type
Fluid temperature
Temperature sensors
Electronic adjuster
Fixed-point temperature adjustment range
Climatic function limits
Precision
Serial interface
Communication protocol
Recirculation pump relay flow
Input signals
Output signals
Cable length
Maintenance
Certification
IP65
-10°C to 50°C, UR max 85%
Water, water with glycol max. 30%
-10°C to +100°C (-20°C to +120°C with spacer)
Contact-type, NTC 10k
Ω
, 80 cm length
PID
Heating: 24°C ÷ 50°C • Cooling: 10°C ÷ 30°C
25°C ÷ 45°C
+/- 1°C
RS485
Modbus RTU
1A
Room thermostat • Summer/winter switch • External temperature sensor
Ambient temperature sensor • Relative humidity sensor
Indication of seasonality • activation of adiabatic dehumidifier
Activation of integration function
80 cm
None
CE
DIAMIX PR / COMPAMIX PR
COMPARATO NELLO SRL
REMOTE MANAGEMENT
DIAMIX PR
and
COMPAMIX PR
are equipped with a MODBUS RTU interface; using the RS485 serial connection, it is possible to modify all the operating parameters, send commands to the valve, receive in-
formation on the operating status and perform diagnostics.
The
DIAMIX PR / COMPAMIX PR
mixing valves can be connected to the modern Building Management Systems (BMS).
TECHNICAL FEATURES OF THE ACTUATOR
•
•
Tracking cooling adjustment
The delivery temperature Tset_point for cooling is automatically calculated by the software as a function of the dew point temperature. The dew point temperature is calculated by means of the relative humidity
and ambient temperature sensor (optional cod. RFTRUEE10).
T_setpoint = Tr CI3 where:
Trujade = Dew temperature calculated from relative humidity and ambient temperature.
CI3 = temperature constant adjustable between -3°C and +3°C.
The function also regulates the relative humidity in the environment: the dehumidifier can be activated by means of a digital output when the relative humidity falls below the “CI1” threshold. Thanks to the special
digital output it is possible to activate the integration mode of the dehumidifier: When the ambient temperature exceeds the value “CI2”, the contact is closed so that the dehumidifier injects dry air into the house
at a temperature lower than the ambient temperature.
Electronic security:
It is possible to set two limit temperature for the fluid: one for winter heating and one for summer cooling.
P3 = heating mode max temperature, adjustable between 50°C and 60°C
P4 = cooling mode min temperature, adjustable between 5°C and 13°C
When these values are exceeded, the mixing valve enters the “safety” mode: it stops the pump and connects the common (mixed) way to the system return and then blocks any active function.
The display alternatively shows the "ALt" notice and the real-time temperature detected by the outlet sensor.
The system resumes normal operation only when the temperature is back within the normal operation range.