RA8000 and ESA12000 Storage Subsystems
2–30
387404–001
EK–SMCPR–UG. A01
2.4.4 Installing a Filler Panel Mounting Kit in a 41U RETMA Cabinet
This procedure describes how to install the filler panel mounting kit (DS-SWX41-XK)
into the 41U RETMA cabinet.
NOTE
If a cabinet has a particular filler panel configuration that
was factory installed, do not remove the panels unless you
are reconfiguring the cabinet. If adding enclosures or
reconfiguring the cabinet, use filler panels in all open
cabinet slots.
2.4.4.1
Installation Procedure
NOTE
The panels in the mounting kit are stamped with identifying
part numbers. Also, not all of the parts are used in each
cabinet configuration.
1. Unpack and inspect the contents of the panel mounting kit. It should contain the
following components:
Description
Qty.
1 Unit (1U) Filler Panel
4
5 U Filler Panel
1
1U Cover Plate
1
10-32 x 5/8 Pan-Head SEMS Screws
14
U-Nut
14
The filler panels and cover plate in this kit mount in either a 1U space or 5U space. A
single U-space (1U) is composed of three rail holes and measures 1.75 inches in height.
Spacing between the first and second hole, and between the second and third hole in a U-
space is 0.625 in. Spacing between the third hole in a U-space and the first hole of a
second U-space is 0.5 in. Thus, a 1U space measures 1.75 in (0.625 + 0.625 + 0.5). This
three hole pattern repeats the entire length of the rails in a 41U RETMA cabinet.