7
.
Installation Guidelines
PowerShift User Manual Version B
Page 23
g. To troubleshoot any issues or when ready to connect the Remote, it will be
necessary to power off the circuit. Note the following:
NOTE
: After powering off the circuit, wait about 2-3 minutes for the
capacitive jumper to discharge before proceeding. The capacitor voltage
will always be less than 60VDC safety limit (and thus there is no personal
safety issue), but waiting a few minutes will minimize any negligible spark
that may occur when the cable is reconnected to the RRU.
h. Connect the capacitive jumper output cable to the Remote (when the
connection is made there may be a negligible spark due to any small
charge remaining on the capacitive jumper)
i. Close the applicable DC power breaker to power the circuit, confirm the
calibration sequence completes successfully, and confirm the Remote
powers up
j. Continue with the cabling and power up of the remaining Remotes