For finished concrete bricks
Install the hanging hook with expansible bolt into the concrete deep to 45~50mm to prevent loose.
Steel roof beam structure
Install the supporting angle steel.
Hoisting the indoor unit
Adjust the height of screw 2, to make the difference between the upper surface of gasket 2 and the
lower surface of the ceiling is 70mm;
Hoisting the unit on the suspender bolt as the follow figure display, use the level gauge to level-out the
length and width directions, and it needs to repeatedly adjust four screw 2 of the suspender during the
process. It might occur this situation: under making sure the unit level, the difference of four gasket 2
of the hoisting bolt and the lower surface of the ceiling will be discorded, can’t be 70mm. At this time it
should make sure the level of the unit body, and move the whole unit up and down, and make the four
differences try to be close to 70mm;
Finish adjusting the unit height and the level, fasten the screw 1 of the four suspenders, and make the
unit fixed reliably.