CLIFC-W 201506
Clima Flex Two-pipe One-way Cassette
27
10.4 Install the connection pipe
Connecting pipes
Before connecting the pipes, make sure the seal washers located inside the connecting nut.
Connect the unit to the water system by means of the fittings which are marked inlet and outlet.
Avoid the damage to screw thread of evaporator, do not overexertion, when screwing. For avoid
non-screw up or damage of screw thread, two spanners must be used simultaneously.
Lag the connection pipes and any valves with anti-condensation material 10 mm thick or install the
auxiliary.
Ensure all interfaces not water leakage.
Air Exhaust
When finished pipes and junctions connection. Turn the turnbuckle down, find the air release valve
inside the unit, and exhaust the air contained in the circuit.