Service Manual -
SVH 09/12/18/24 Series
46
42
9.3.8 Over voltage or too low voltage protection diagnosis and solution
(P1)
Error Code
P1
Malfunction conditions
An abnormal voltage rise or drop is detected
when
checking
the specified voltage detection circuit.
Possible
causes
●
Power supply problems.
●
System leakage or block
age
●
PCB faulty
Troubleshooting:
Check the power supply
.
OK?
Check the connections and
wires
. OK?
Stop the unit
No
Yes
No
Correct the connections or
replace the wires.
Yes
Replace the reactor
Yes
No
Replace the IPM board
Check the voltage between
P and N
. OK?
Check the reactor
.
OK?
Yes
No
Replace outdoor main PCB
Remark:
Measure the DC voltage
between P and N port. The
normal value should be
around 310V.
P
N