33
9.3.4 Fan speed has been out of control diagnosis and solution
(E3)
Error Code
E3/F5
Malfunction conditions
When indoor fan speed
remains
too low (300RPM) for certain
time, the unit will stop and the LED will display the failure.
Possible
causes
●
Wiring
error
●
Fan ass
embl
y faulty
●
Fan motor faulty
●
PCB faulty
Troubleshooting:
Power off, then restart the
unit 2 minutes later
. Does
unit operate normally?
Shut off the power supply
.
Can you r
otate the fan by hand
?
Issue resolved.
Find out the cause and
re
solve
.
Check the wiring of
fan motor
. OK?
Yes
No
No
Correct the connections.
No
No
Replace the fan motor
. OK?
Yes
Yes
Measure the voltage for the
fan motor from the main
PCB refer to the
Appendix
1
. OK?
Yes
Replace the main PCB
No