Service Manual -
SVH 09/12/18/24 Series
16
14
pumping 50 minutes, please check if there are
some leakage points. Fully close the handle Lo
valve of the manifold valve and stop the
operation of the vacuum pump. Confirm that the
gauge needle does not move (approximately 5
minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about
45°counterclockwise for 6 or 7seconds after the
gas coming out, then tighten the flare nut again.
Make sure the pressure display in the pressure
indicator is a little higher than the atmosphere
pressure. Then remove the charge hose from
the 3 way valve.
8) Fully open the 2 way valve and 3 way valve
and securely tighten the cap of the 3 way valve.
6.7 Re-installation
after
the outdoor unit
has
been
repaired
1. Evacuation for the whole system
Procedure:
1) Confirm that both the 2-way and 3-way
valves are set to the opened position.
2) Connect the vacuum pump to 3-
way valve’s
service port.
3) Evacuation for approximately one hour.
Confirm that the compound meter indicates
-0.1Mpa
(14.5
Psi).
4) Close the valve (Low side) on the charge set,
turn off the vacuum pump, and confirm that the
gauge needle does not move (approximately 5
minutes after turning off the vacuum pump).
5) Disconnect the charge hose from the vacuum
pump.
2. Refrigerant charging
Procedure:
1)
Connect the charge hose to the charging
cylinder, open the 2-way valve and the 3-way
valve
Connect the charge hose which you
disconnected from the vacuum pump to the
valve at the bottom of the cylinder. If the
refrigerant is R410A, make the cylinder bottom
up to ensure liquid charge.
2)
Purge the air from the charge hose
Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air (be careful of the liquid
refrigerant).
3)
Put the charging cylinder onto the electronic
scale and record the weight.
4)
Open the valves (Low side) on the charge set
and charge the system with liquid refrigerant If
the system cannot be charge
d
with the specified
amount of refrigerant, or can be charged with a
little at a time (approximately
5 oz.
each time) ,
operating the air conditioner in the cooling
cycle; however, one time is not sufficient, wait
approximately 1 minute and then repeat the
procedure.
5)
When the electronic scale displays the proper
weight, disconnect the charge hose from the 3-
way valve’s service port immediately
If the system has been charged with liquid
refrigerant while operating the air conditioner,
turn off the air conditioner before disconnecting
the hose.
6)
Mount the valve stem caps and the service
port. Use torque wrench to tighten the service
port cap to a torque of 18N.m. Be sure to check
for gas leakage.
Summary of Contents for A-SVH09SA-0
Page 7: ...Service Manual SVH 09 12 18 24 Series 7 2 2 Indoor Outdoor units ...
Page 10: ...Service Manual SVH 09 12 18 24 Series 10 For Mounting Plate D ...
Page 30: ...Service Manual SVH 09 12 18 24 Series 30 For A SVH09SA 1 A SVH12SA 1 ...
Page 31: ...Service Manual SVH 09 12 18 24 Series 31 For A SVH18SA 1 A SVH24SA 1 ...
Page 44: ...Service Manual SVH 09 12 18 24 Series 44 P W N U ...
Page 45: ...Service Manual SVH 09 12 18 24 Series 45 41 N V N W ...