Description of the UPS operation modes 

Operating mode 

Description 

LCD state 

Normal mode 

(On Line) 

If the supply voltage is within tolerance, the UPS 
supplies the loads with clean and stable voltage 
with  a  sinusoidal  shape.  In  this  mode,  the 
batteries are charged. 

 

ECO mode 

Economy mode 
If  the  supply  voltage  is  within  tolerance,  the 
supply  voltage  is  supplied  directly  to  the  UPS 
output. The inverter is in Stand-by mode, which 
increases  efficiency  and  reduces  operating 
costs. 

 

Frequency 

converter mode 

If  the  supply  voltage  frequency  is  within  the 
range of 40 ÷ 70Hz, it is possible to set a fixed 
value of the output voltage frequency of 50 or 
60Hz. This mode also charges the batteries. 

 

Battery 

operation mode 

In  the  event  of  a  power  failure  or  when  the 
supply  voltage  is  out  of  tolerance,  the  UPS 
transfers to battery operation. A beep is made 
every 4 seconds. 

 

Bypass mode 

If  the  mains  voltage  is  within  the  acceptable 
tolerance  limits,  but  an  overload  or  any  other 
event  occurs,  the  UPS  will  switch  to  Bypass 
mode. A beep is made every 10 seconds. In this 
mode, the batteries are charged. 

 

Stand-by mode 

UPS  is  turned  off,  no  voltage  is  applied  to  the 
output. In this mode, the batteries are charged. 

 

Alarm 

In  emergency  mode,  the  UPS  shows  the  error 
code and the icons associated with the event. 

 

 

 
 

Summary of Contents for COVER Basic 1K

Page 1: ...h against fire To the connector marked EPO connect the emergency switch against fire The standard configuration of the EPO is an NC normally closed type connector i e for the correct operation of the...

Page 2: ...UPS to activate the test OFF ENTER UPS shutdown Press and hold for 2 seconds to turn off the UPS or switch to Bypass mode depending on the selected operation configuration options Confirm Selection P...

Page 3: ...on programmable outputs Indicates whether a programmable socket group is configured Information about the operating mode Indicates that the UPS is connected to the 230V mains Indicates the UPS is runn...

Page 4: ...erter available not available ENA Converter function available DIS Converter function unavailable default 03 Frequency setting Frequency setting for battery operation BAT 50 50Hz output frequency BAT...

Page 5: ...olds results in the inaccessibility of the bypass path HLS Bypass high voltage threshold Using the arrow keys it is possible to select the voltage of 230V 264V default 264V LLS Bypass low threshold Us...

Page 6: ...the range of 40 70Hz it is possible to set a fixed value of the output voltage frequency of 50 or 60Hz This mode also charges the batteries Battery operation mode In the event of a power failure or w...

Page 7: ...s Battery failure Beep every 2 seconds UPS off Bypass out of tolerance Beep every 2 seconds Bypass frequency unstable Beep every 2 seconds Error EEPROM Beep every 2 seconds Fan error Beep every 2 seco...

Page 8: ...tion follow the instructions on the computer screen You must restart your computer after the installation process is complete Restarting the computer will automatically launch ViewPower as shown by th...

Reviews: