UPS settings menu
Use in the UPS configuration menu is possible when the UPS is turned off (Stand-by or Bypass mode).
To enter the configuration menu, press the SELECT key for 5 seconds.
View of the configuration menu and description of the possible settings below.
Parameter 1
Indicates the number assigned to a specific parameter as
described below, e.g. 01 - output voltage.
Parameter 2 and 3
Indicates a value specific for a given parameter, e.g. 230 -
output voltage value.
Display state
Settings
01 - Setting the output voltage value
200: Indicates 200Vac output voltage
208: Indicates 208Vac output voltage
220: Indicates 220Vac output voltage
230: indicates 230Vac output voltage (default)
240: Indicates 240Vac output voltage
02 – Frequency converter available / not available
ENA: Converter function available
DIS: Converter function unavailable (default)
03 - Frequency setting
Frequency setting for battery operation:
BAT 50: 50Hz output frequency
BAT 60: output frequency 60Hz
If the frequency converter function is available, the frequency of the
output voltage can be selected:
CF 50: 50Hz output frequency
CF 60: 60Hz output frequency
04 – ECO mode
Setting the availability of economy mode (ECO mode)
ENA: ECO function available
DIS: ECO function unavailable (default)
05 – Voltage tolerance range in ECO mode
Settings of the lower and upper tolerance of the supply voltage for the ECO / AECO
mode.
HLS: upper range of the supply voltage. Using the arrow keys it is possible to select
the range + 7V ÷ + 24V from the nominal value, e.g. 230V (d 12V).
LLS: lower range of the supply voltage. Using the arrow keys it is possible to select
the range 77V ÷ -24V from the nominal value, e.g. 230V (default -12V).