UPS settings menu 

Use in the UPS configuration menu is possible when the UPS is turned off (Stand-by or Bypass mode). 
To enter the configuration menu, press the SELECT key for 5 seconds. 
View of the configuration menu and description of the possible settings below. 
 
Parameter 1 
Indicates the number assigned to a specific parameter as 
described below, e.g. 01 - output voltage. 
 
Parameter 2 and 3  
Indicates a value specific for a given parameter, e.g. 230 - 
output voltage value. 
 
 
 

Display state 

Settings 

01 - Setting the output voltage value 

 

200: Indicates 200Vac output voltage 
208: Indicates 208Vac output voltage 
220: Indicates 220Vac output voltage 
230: indicates 230Vac output voltage (default) 
240: Indicates 240Vac output voltage 

02 – Frequency converter available / not available 

 

ENA: Converter function available 
DIS: Converter function unavailable (default)

 

03 - Frequency setting 

 

Frequency setting for battery operation: 
BAT 50: 50Hz output frequency 
BAT 60: output frequency 60Hz 
If the frequency converter function is available, the frequency of the 
output voltage can be selected: 
CF 50: 50Hz output frequency 
CF 60: 60Hz output frequency 

04 – ECO mode 

 

Setting the availability of economy mode (ECO mode) 
ENA: ECO function available 
DIS: ECO function unavailable (default)

 

05 – Voltage tolerance range in ECO mode 

 

Settings of the lower and upper tolerance of the supply voltage for the ECO / AECO 
mode. 
HLS: upper range of the supply voltage. Using the arrow keys it is possible to select 
the range + 7V ÷ + 24V from the nominal value, e.g. 230V (d 12V). 
LLS: lower range of the supply voltage. Using the arrow keys it is possible to select 
the range 77V ÷ -24V from the nominal value, e.g. 230V (default -12V).

 

Summary of Contents for COVER Basic 1K

Page 1: ...h against fire To the connector marked EPO connect the emergency switch against fire The standard configuration of the EPO is an NC normally closed type connector i e for the correct operation of the...

Page 2: ...UPS to activate the test OFF ENTER UPS shutdown Press and hold for 2 seconds to turn off the UPS or switch to Bypass mode depending on the selected operation configuration options Confirm Selection P...

Page 3: ...on programmable outputs Indicates whether a programmable socket group is configured Information about the operating mode Indicates that the UPS is connected to the 230V mains Indicates the UPS is runn...

Page 4: ...erter available not available ENA Converter function available DIS Converter function unavailable default 03 Frequency setting Frequency setting for battery operation BAT 50 50Hz output frequency BAT...

Page 5: ...olds results in the inaccessibility of the bypass path HLS Bypass high voltage threshold Using the arrow keys it is possible to select the voltage of 230V 264V default 264V LLS Bypass low threshold Us...

Page 6: ...the range of 40 70Hz it is possible to set a fixed value of the output voltage frequency of 50 or 60Hz This mode also charges the batteries Battery operation mode In the event of a power failure or w...

Page 7: ...s Battery failure Beep every 2 seconds UPS off Bypass out of tolerance Beep every 2 seconds Bypass frequency unstable Beep every 2 seconds Error EEPROM Beep every 2 seconds Fan error Beep every 2 seco...

Page 8: ...tion follow the instructions on the computer screen You must restart your computer after the installation process is complete Restarting the computer will automatically launch ViewPower as shown by th...

Reviews: