5
06 – Bypass availability while the inverter is turned off
Bypass availability setting when the UPS has the inverter turned off
(UPS in Stand By mode).
EAW: Bypass available
DIS: Bypass unavailable (default)
07 – Voltage tolerance range for Bypass
Setting the lower and upper tolerance of the supply voltage for the
Bypass. Exceeding the declared voltage thresholds results in the
inaccessibility of the bypass path.
HLS: Bypass high voltage threshold. Using the arrow keys it is possible
to select the voltage of 230V ÷ 264V (default 264V).
LLS: Bypass low threshold. Using the arrow keys it is possible to select
the voltage 170V ÷ 220V (170V by default
08 - Battery autonomy limitation
Setting the maximum battery life 0 - 999 minutes.
DIS: Restriction lock. Autonomy depending on battery capacity.
(Default)
Warning! Setting the value to "0" means an autonomy of 10 seconds.
00 – Exit the settings menu
Exits the UPS configuration menu.