background image

 

 

06 – Bypass availability while the inverter is turned off 

 

Bypass availability setting when the UPS has the inverter turned off 
(UPS in Stand By mode). 
EAW: Bypass available 
DIS: Bypass unavailable (default)

 

07 – Voltage tolerance range for Bypass 

 

Setting the lower and upper tolerance of the supply voltage for the 
Bypass.  Exceeding  the  declared  voltage  thresholds  results  in  the 
inaccessibility of the bypass path. 
HLS: Bypass high voltage threshold. Using the arrow keys it is possible 
to select the voltage of 230V ÷ 264V (default 264V). 
LLS: Bypass low threshold. Using the arrow keys it is possible to select 
the voltage 170V ÷ 220V (170V by default 

08 - Battery autonomy limitation 

 

Setting the maximum battery life 0 - 999 minutes. 
 
DIS:  Restriction  lock.  Autonomy  depending  on  battery  capacity. 
(Default) 
Warning! Setting the value to "0" means an autonomy of 10 seconds. 

00 – Exit the settings menu 

 

Exits the UPS configuration menu. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for COVER Basic 1K

Page 1: ...h against fire To the connector marked EPO connect the emergency switch against fire The standard configuration of the EPO is an NC normally closed type connector i e for the correct operation of the...

Page 2: ...UPS to activate the test OFF ENTER UPS shutdown Press and hold for 2 seconds to turn off the UPS or switch to Bypass mode depending on the selected operation configuration options Confirm Selection P...

Page 3: ...on programmable outputs Indicates whether a programmable socket group is configured Information about the operating mode Indicates that the UPS is connected to the 230V mains Indicates the UPS is runn...

Page 4: ...erter available not available ENA Converter function available DIS Converter function unavailable default 03 Frequency setting Frequency setting for battery operation BAT 50 50Hz output frequency BAT...

Page 5: ...olds results in the inaccessibility of the bypass path HLS Bypass high voltage threshold Using the arrow keys it is possible to select the voltage of 230V 264V default 264V LLS Bypass low threshold Us...

Page 6: ...the range of 40 70Hz it is possible to set a fixed value of the output voltage frequency of 50 or 60Hz This mode also charges the batteries Battery operation mode In the event of a power failure or w...

Page 7: ...s Battery failure Beep every 2 seconds UPS off Bypass out of tolerance Beep every 2 seconds Bypass frequency unstable Beep every 2 seconds Error EEPROM Beep every 2 seconds Fan error Beep every 2 seco...

Page 8: ...tion follow the instructions on the computer screen You must restart your computer after the installation process is complete Restarting the computer will automatically launch ViewPower as shown by th...