68
IE-LGR-UxxxxM-22
Annex 6: SMS message format
SMS message format for SYSTEM ALARM:
The message header includes:
SYSTEM ALARM<enter>
„Description of the device DescDev“<enter>“
Depending on the type of alarm, the corresponding text:
Data memory limit overflow,
Battery warning,
Battery empty,
Battery Ok,
External power lost,
External power Ok;
Date/Time Error,
Date/Time Ok;
Measuring Error on input: ….;
Measuring Error END on input: ….,
Configuration error,
Configuration Ok,
The time of the event, such as „20170808 10:44“
Texts are fixed, user-immutable, if multiple events occur simultaneously
and the length of the message exceeds 160 characters (max message length),
then they will be divided into multiple messages.
Format of alarm SMS message from measured value:
Description of the device DescDev .... max. 32 chars <enter>
Name of the measured location: max. 16 chars <enter>
Te
xt „Actual value:
measured value + unit (or binary input status)<enter>
Text ¨ALARM¨
or
(Text „ALARM END“) <enter>
Description of the alarm: max. 16 chars
Separator comma + gap
Start time / end time of the alarm, such as 2016/05/08 10:44 <enter>
Text „ALARM“ (Text „ALARM END“)
In the case of other alarms followed by <enter> and continues with information
about the next alarm
Description of the alarm:
max. 16 chars
Separator comma + gap
2 chars
Start time of the alarm, such as 2016/05/08 10:44
: :
: :
The length of one message is limited to 160 characters, if there is a requirement
to send more characters, the characters are divided into more messages.
Summary of Contents for U0110M
Page 5: ...IE LGR UxxxxM 22 5 Datalogger UxxxxM U0141M model...
Page 60: ...60 IE LGR UxxxxM 22 Dimensions U0110M U8410M U0121M...
Page 61: ...IE LGR UxxxxM 22 61 U0141M U3120M U4440M...
Page 62: ...62 IE LGR UxxxxM 22 U3121M U3631M...
Page 63: ...IE LGR UxxxxM 22 63 U0141TM U0843M U5841M U6841M U7841M...