background image

Instruction for use of logger S7021 

 

Logger is designed for monitoring and record of digital signals from external devices. It is 

equipped with input for pulse counting and binary input for record of time event. Signals are 
connected by means of the connector. Counter reading and actual state of binary input are displayed 
on dual line LCD are stored in adjustable interval to internal non-volatile memory. Input pulse 
signal is recalculated and displayed in real measured physical units by means of the PC software. 
All logger setting and control are done by means of the computer and can be protected by password. 
Logging start/stop is enabled: at certain time and date programmed from computer, by external 
signal connected to binary input or by delivered magnet). Switching ON and OFF is enabled also by 
external binary signal of channel 4. 

It is also possible to operate logger with switched OFF display. Short display of actual 

measured values is enabled by means of magnet. 

Switched ON logger every 10 s (independently on programmed logging interval) updates 

display reading, compares counter reading with two adjustable limits and indicates alarms on the 
display. Two alarm modes are enabled: instant or with memory (detected alarm is indicated 
permanently till alarm memory is cleared from the PC – useful if counter overflow is enabled). 
Alarm function can be enabled or disabled. Binary channel has no alarm function. 

Counter can be configured as 16 bits (higher maximum number of recorded values) or 32 bits 

(higher counter range). Counter stops after filling the maximum value and logger is switched OFF 
with the message on the LCD. If needed counter mode can be selected, when after fulfilling counter 
overflows and continues from value 0. 

Logging mode can be adjusted as non-cyclic, when logging stops after filling the memory. In 

cyclic mode oldest stored values are overwritten by new. In addition logging mode can be selected 
when logging is active only if measured value is out of adjusted alarm limits. 

Stored values can be transferred from logger memory to the PC by means of communication 

adapter. Communication adapter can be connected to the logger permanently – data logging is not 
interrupted even if data download appears.  

Logger evaluates minimum battery voltage and its drop below allowed limit is indicated on the 

display. At the same time value of remaining battery capacity is available by means of the PC 
program and appears on the logger LCD in % (every time after switch ON). 

  

 
 
Technical parameters of the instrument: 

 

 
Counter input (logger channel 1): 
  Counter range: in 16 bits mode 0 to 61 695 values 

  in 32 bits mode  0 to 2 021 654 527 values 

Maximum counter value displayable on the LCD: 19999, 0 to 3 digits right from decimal 

point 
  Signal for counter input: from potential-less contact or binary voltage signal 
  Minimum pulse duration at counter input: 1 ms (shorter pulses may not be recorded) 
  Maximum frequency at binary input: 500 Hz 
  Current through closed contact: 30 

µ

  Voltage across opened contact: 3.6 V 
  Low voltage level: 0 to +0.2 V (maximum current from input 30 

µ

A) 

  High voltage level: +3.0 to +30 V (maximum current to input 100 nA) 
  Incrementing of counter: by leading edge (by contact opening) 
Binary input (logger channel 4): 
  Signal for binary input: from potential-less contact or binary voltage signal 

 

  IE-LOG-S7021-04 

Summary of Contents for S7021

Page 1: ...LOGGER S7021 Dual channel logger with counter and binary inputs Instruction for use...

Page 2: ...aximum value and logger is switched OFF with the message on the LCD If needed counter mode can be selected when after fulfilling counter overflows and continues from value 0 Logging mode can be adjust...

Page 3: ...me clock adjustable from computer integrated calendar including leap years Error of internal RTC 200 ppm i e 0 02 17 28 s in 24 h Power Lithium battery 3 6 V size AA Battery life typical data download...

Page 4: ...setting of the instrument accordingly to the user needs menu Configuration Setting of instrument parameters Before logging start it is necessary check or optionally set the logger real time clock sele...

Page 5: ...e logger LCD indication ON and OFF is displayed permanently Selection of display of increments at the card of counter channel setting causes record of counter increments in time specified by logging i...

Page 6: ...mperature range battery life can be reduced to 75 i e if displayed remaining battery capacity drops below 25 it is recommended to replace the battery If LCD is switched ON actual readings are displaye...

Page 7: ...ation decimal point goes out logger would be switched OFF Display goes out automatically after 30 s Remove magnet from slots anytime during display is ON or later Activation of switched OFF LCD for 30...

Page 8: ...clock setting below critical limit or battery disconnection for longer period than approximately 30 s after display switch ON during date and time display all four arrows appears as warning to check o...

Page 9: ...s identical with the above procedure for switching ON If decimal point does not appear after 1 s it is necessary remove the magnet and repeat the procedure Logger connection to monitored device by the...

Page 10: ...l logger settings remain unchanged In the opposite case check by means of PC program all settings especially the real time clock in logger Attention inserted battery with incorrect polarity causes log...

Reviews: