SUPERVISOR:
the supervisor function sends a command directly to the system supervisors, for example Planux Manager, Serial
Bridge, Minitouch. This command is used by the supervisors to activate internally stored commands, or to use the input status
for logic rules or other functions. You must set the number of the supervisor input to send.
For example, if you want to use a button to activate a scenario stored in the memory of a Planux Manager or Minitouch
supervisor, you must set the input in this way. This also applies if you want to use an input status for a logic or link function on
the serial bridge.
TYPE OF MESSAGE
NORMAL:
the module sends a command to the addressee, switching the output for which it was programmed.
For example, if you send a normal command to a timed output, the output will be activated for the set time; if you send a normal
command to an output set as bistable, the output inverts its status.
SET:
the module sends a “forcing ON” command and the output is then activated independently of the programming, remaining
active until a new command is sent. The SET command does not affect outputs set as "Rolling shutter".
For example, if you want to send an activation command to a group of lights, the SET command type must be set; this switches
on any lights which are off and leaves those already switched on running. If a SET is sent to an output set as timed, the output
is activated and will remain active until a new command is received.
RESET:
the module sends a “forcing OFF” command and the output is then deactivated independently of the programming,
remaining inactive until a new command is sent. If the RESET command is sent to an output programmed as "Rolling shutter",
the relay is not activated and the shutter to which it is connected will not move.
For example, to send a deactivation command to a group of lights, the RESET command type must be set; this switches off any
lights which are on and leaves those already switched off inactive.
ANALOGUE ON:
the module sends the activation command to the set analogue output, bringing the output to the last value set
temporarily. This is used, for example, to switch on dimmable lights connected to modules Art. 20046810 or Art. 20046851.
ANALOGUE OFF:
The module sends the off command to the set analogue output. This is used, for example, to switch off dimmable
lights connected to modules Art. 20046810 or Art. 20046851.
106
Summary of Contents for simplehome
Page 1: ...www comelitgroup com EN TECHNICAL MANUAL Technical manual for the SimpleHome system...
Page 35: ...Fastening Unfastening Sensor mounting 35...
Page 41: ...150 cm 120 cm Minitouch timer thermostat mounting 41...
Page 45: ...Minitouch mounting 150 cm 120 cm 45...
Page 76: ...Load management module 76...
Page 78: ...78...
Page 107: ...107...
Page 108: ...7 edizione 03 2014 cod 2G40001063...