Atena Easy Addressable Fire Alarm Panel – Installation and Programming Manual
5
9
groups for zones’ organization
5 monitored potential outputs:
o
SND1 (Sounder 1)
o
SND2 (Sounder 2)
o
FIRE
o
FAULT (The output is deactivated in case of fault event.)
o
EXT (Extinguishing/ Fire Protection
– An output for sending an fire alarm signal to automatic fire
extinguishing system)
3 specialized inputs:
o
In AmC* (Input Alarm Confirmation)
o
In PC* (Input Protection Alarm Confirmation)
o
In FP* (Input Fault Protection Panel)
* Covers the requirements on standard VdS 2540
4 non-monitored, programmable relay outputs with parameters: 15A@24VDC
Display
– letter and digits LCD module (4 rows х 40 symbols)
Built-in real time clock, supported from integrated lithium battery - 3V, CR3032 type
Memory log file for up to 10000 system events
Comprehensive day/night mode facility
2 Steps of alarm levels (T1 and T2)
Supports external thermo printer
Multilanguage support for operation menus
Easy software update via computer or USB drive
Designed according the requirements of EN54-2/4
Metal box cabinet for wall mounting: bottom
(306х412х81mm) and cover (310х416mm)
1.2.2 Possible Hardware Configurations
Minimal Configuration
o
Control panel (main PCB with one built-in loop controller)
o
Indication (indication PCB with mounted LCD module)
o
Power supply source
Maximal Configuration
o
Control panel (main PCB with one built-in loop controller)
o
Indication (indicator PCB with mounted LCD module)
o
Power supply source
o
Loop controller (for the second loop)
o
Communication module
o
RS485 Redundant Network controller
1.2.3 Environment
Degree of protection: IP30
Operation temperature: -5
ºС up to +40ºC
Relative humidity:
до 95% (without condense)
Storage temperature: -
10ºС up to +60ºC
Weight (without the battery): ~ 4.2 kg.
1.2.4 Electrical Characteristics
Earth Connection
The earth connection has to be realized in accordance with the rules for the electrical safety with the total resistance in
the circuit lower than 10Ω. It is mandatory to connect the main power supply cable to the middle input of the fire panel
terminal
– see also item 2.4 Main power connection.
ATTENTION: Do not instal the fire panel near power electromagnetic fields (radio equipment,
electric motors, etc.)!