Atena Easy Addressable Fire Alarm Panel – Installation and Programming Manual
36
41IOM010
– Mini input module
The 41IOM010 is a compact module with one input. The module monitors and transfers to control panel the state of
this input - state ON or state OFF. 41IOM010 is designed for built-in installation in the mounting box of a device.
The activation of the 41IOM010 input can be programmed according the application. To program the generated event
at the input, press button
(1) IN
– in the submenu are active three fields for setting:
GENERATES
–
Use the up/ down arrow buttons to select generated event at the input: FIRE/ EVACUATE/
RESET/ MESSAGE ALARM/ MESSAGE FAULT/ MESSAGE WARNING/ SILENCE BUZZER/ SILENCE
ALARM/ CLASS CHANGE*/ SILENCE ALARM (STROBE ON)**
DELAY
–
The field is common for all events. Enter time delay 0-600 sec for activation event.
NAME
–
Enter a specific name for the
module’s input.
* CLASS CHANGE - To use the class change function, connect the terminals of a switch with normally open contacts
to the module terminals.
** SILENCE ALARM (STROBE ON)
– Use to disable the sounders in case of evacuation event, for example when
using the panel together with a separate Voice Evacuation System. The sounders will be silent, but their LED
signalization will be active (41SAI000 and 41SCI000) regardless their individual settings.
Use the left and right arrows to switch over the GENERATES, DELAY and NAME fields.
(2) GROUP
- Press the functional button to enter in submenu for group selection. In the editing field enter the group
number using the up/ down arrow buttons.
All set parameters are confirmed with ENTER button. The exit to the main screen of DEVICES SETUP menu is with
pressing CANCEL button.
41IOM004
– Module with 4 outputs
The programming is same for all of the outputs. Use the functional buttons to select an output number.
To program OUT 4 you have to press button MORE >>. To see the ID number of the module press MORE >> button
again.
and
Press