Reflect-O-Ray
®
Oil Fired EDS 3.5
Installation, Operation & Service
Page 38
Combustion Research Corporation
ELECTRONIC PROVEN SPARK IGNITION
CONTROL WITH 100% LOCKOUT:
APPLICATION
The solid state ignition control will ignite the oil by spark.
The oil is ignited and burns during each running cycle.
Should a loss of flame occur, the main valve closes and
the burner will lockout. This control has an internal 100%
lockout function to completely shut down the system
should the oil fail to ignite within 5 seconds. To initiate a
re-ignition trial when lockout occurs, the power must be
interrupted for 5 minutes.
The solid state ignition control must not be subjected to
temperatures below -40°F (-40°C) or above 150°F (66°C).
CAUTION: When servicing the Riello burner assembly
use only Riello components.
OIL SUPPLY FAILURE ON START
1. Thermostat calls for heat.
2. Airflow is proven.
3. Valve and spark are energized after pre-purge.
4. After a maximum 5 second trial for ignition, the system
will lockout to completely disarm the system.
5. In order to initiate a re-ignition trial, the power must be
interrupted for 5 minutes. Reset the ignition control by
pushing the illuminated button on the back of the
burner assembly. DO NOT push the reset button more
than two (2) times.
POWER INTERRUPTION ON START:
1. No oil will flow during power interruption.
2. Normal sequence will resume when power is restored.
POWER INTERRUPTION DURING RUNNING
CYCLE:
1. Valve is de-energized.
2. Valve and spark are energized when power is restored
and normal sequence will resume.
TURNING OFF THE APPLIANCE:
VACATION SHUTDOWN
-- Set the thermostat to the
desired room temperature while you are away.
COMPLETE SHUTDOWN
– Shut off the fusible link valve
on each burner, shut off the main valve on the oil supply
tank and remove power from the system. Follow the
Lighting Procedure to resume normal operation.
WARNING
FIRE OR EXPLOSION HAZARD
IMPROPER INSTALLATION, ADJUSTMENT,
ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE DEATH, SEVERE INJURY
AND/OR PROPERTY DAMAGE.
1. Flame is lit automatically. Do not light the flame
manually.
2. Before automatic lighting of the burner inspect
around the appliance for any fuel oil leaks.
3. IF YOU HAVE AN FUEL OIL LEAK:
♦
Turn off the fusible oil valve at the appliance.
Remove power from any oil supply system and
close the valve on the main fuel tank.
♦
Do not light any appliances within the vicinity of the
fuel leak.
♦
Contact your service technician or oil supplier for
assistance. If you cannot reach your oil supplier or
service technician and you have sizable fuel oil leak,
call the fire department.
MAINTENANCE:
STOP: READ ALL
WARNINGS
WARNING
FIRE OR EXPLOSION HAZARD
IMPROPER INSTALLATION, ADJUSTMENT,
ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE DEATH, SEVERE INJURY
AND/OR PROPERTY DAMAGE.
Do not disassemble the oil control. The oil control
contains no replaceable components. Attempted
disassembly or repair may damage the oil ignition
control. Improper cleaning or re-assembly may cause
oil leakage. When cleaning, ensure that the burner
assembly is reassembled properly and inspected for oil
leaks.
!
!