Reflect-O-Ray
®
Oil Fired EDS 3.5
Installation, Operation & Service
Combustion Research Corporation
Page 27
VENTING ARRAGENMENTS
For Reflect-O-Ray
®
OIL FIRED EDS 3.5
S
ystems
Min. 2"
Max. 12"
Provide UNISTRUT or Angle Iron
and secure to buildings wall
framing.
Vacuum
Exhauster
Secure to UNISTRUT or
Angle Iron by bolting through
vibration isolators.
Trim any insulation so that a
minimum of 2" clearance is
maintained around exhaust duct.
P
a
rapet
or
adj
oi
ni
ng bui
ld
ing.
6'-0" 9 (183 cm)
Minimum
Min. 2"
Max. 12"
Alternate ceiling mount,
suspend with 4 - 1/4"
(min.) ALL Thread.
DO NOT USE CHAIN
Vacuum
Exhauster
Anchor vacuum exhauster
to wall through vibration
isolators.
For combustible walls a minimum
of 2" clearance around exhaust
duct is required. If necessary
installer shall fabricate exterior wall
flashing (Min. 16 ga. galvinized
steel construction)
P
a
rapet
or
adj
oi
ni
ng bui
ld
ing.
6'-0" 9 (183 cm)
Minimum