Reflect-O-Ray
®
Oil Fired EDS 3.5
Installation, Operation & Service
Page 20
Combustion Research Corporation
TYPICAL DAY TANK INSTALLATION
The following oil supply circuit shows a day tank
arrangement with the burners set up as a two pipe system.
This layout has proven to be an acceptable and reliable
method of oil supply. In all cases it is recommended that
the
Reflect-O-Ray
®
Oil Fired
burners be installed as two
pipe systems.
Install suitable oil filters before the oil supply pump and
secondary filters at each burner assembly. Fusible link oil
valves must be installed in both the supply side (suction)
and return side (discharge) of the burner pump.
Oil level control electrical
connection to supply pump
Vacuum
Breaker
Supply
Line
Return
Line
Pressure
Gauge
Fusible
Link Valve
Check Valve
Fusible Link Valve
Oil Filter
Oil Supply Tank
Day Tank Return Line
Reflect-O-Ray
®
Oil Burner
Reflect-O-Ray
®
Oil Burner
Reflect-O-Ray
®
Oil Burner
Fusible Link
Valves (Typ.)
Oil Filter
(Typ.)
Day Tank
Suc
ti
o
n
15’-0” Lift
Ma
x.
Pre
s
s
u
re Hea
d
35’-0” M
a
x
.