InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
82
Shutdowns
12.3
12.3.1
Shutdown procedure
The
InteliNano
NT
Plus
O05 GCB Close/Open
and
O03 Stop Solenoid
to stop the engine immediately.
O04 Alarm
output is closed. Active or not confirmed protection disables start.
12.3.2
Active unconfirmed shutdown
Stop
button blinks,
the shutdown symbol will blink in the upper right corner of LCD, and the proper shutdown symbol is
displayed in history with running hours stamp. The record in history is negative, see
. See
For shutdown alarm confirmation press
Stop
button.
Figure 12.6
ACTIVE UNCONFIRMED SHUTDOWN
–
E
MERGENCY
S
TOP
12.3.3
Active confirmed shutdown
When an active shutdown is confirmed the red LED above the
Stop
button stops blinking. The record
in history stays negative with confirmation symbol at the end.
Figure 12.7
ACTIVE CONFIRMED SHUTDOWN
–
E
MERGENCY
S
TOP
12.3.4
Inactive unconfirmed shutdown
O04 Alarm
output is closed, red LED above
Stop
button blinks. Shutdown symbol is displayed in
upper-right corner of the LCD, and proper warning symbol is displayed in history with running hours
stamp. See
. See list of
For shutdown alarm confirmation
press
Stop
button
Figure 12.8
INACTIVE UNCONFIRMED SHUTDOWN
–
E
MERGENCY
S
TOP