O02 Fuel Solenoid
This output is dedicated to control the fuel solenoid (valve). The output is closed in the same time as
output and remains closed while the engine is running.
Prestart Time
0 - 600 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Cranging Fail
Pause 8 s
Cranging Fail
Pause 8 s
Gen-set start failed
Starter Output
On
Off
Fuel Solenoid is
opened
Start
Time
Prestart Time
Maximum
Cranking Time
0 - 60 s
On
Off
Time
Start
Engine run
Max. Stab. Time 7 s
Min. Stab. Time
Starter Output
Stop
Fuel Solenoid is
opened