7.4.1 Battery voltage – reading (read multiple registers)
Request:
01 03 00 0C 00 01 44 09
01
= Controller address
See your controller settings
03
= Modbus function code (Read Multiple Registers)
00 0C
= Register address: Register number (Ubat => 40013)
40013 - 40001 = 12 DEC => 000C HEX
See your Cfg Image or list of
communication objects (page 111)
00 01
= Number of registers
40013, it is one register = 01 DEC => 0001 HEX
You have to calculate number of register which
you want read
09 44
= CRC
CRC has to be written LSB then MSB ! See how
to calculate
Response:
01 03 02 00 DC B9 DD
01
= Controller address
See your controller settings
03
= Modbus function code (
)
02
= Length of read data in Bytes (in HEX)
02 HEX => 2 DEC
Define the length of data
Summary of Contents for Inteli Mains NT BaseBox
Page 12: ...IGS NT Communication Guide 12 2 1 IG IS IM NTC BB Communications...
Page 13: ...IGS NT Communication Guide 13 2 2 IG IS IM NTC BB Terminals...
Page 14: ...IGS NT Communication Guide 14 2 3 IG IS IM NTC BB Peripheral modules...
Page 15: ...IGS NT Communication Guide 15 2 4 IG IS IM NTC BB Jumpers settings...
Page 16: ...IGS NT Communication Guide 16 2 5 IG IM NT BB Communication...
Page 17: ...IGS NT Communication Guide 17 2 6 IG IM NT BB Terminal...
Page 18: ...IGS NT Communication Guide 18 2 7 IG IM NT BB Peripheral modules...
Page 19: ...IGS NT Communication Guide 19 2 8 IG IM NT BB Jumper settings...
Page 20: ...IGS NT Communication Guide 20 2 9 IG NT Communications Terminals...
Page 22: ...IGS NT Communication Guide 22 2 11 IM NT Communications Terminals...
Page 23: ...IGS NT Communication Guide 23 2 12 IS NT BB Communications Terminals...
Page 65: ...IGS NT Communication Guide 65...
Page 114: ...IGS NT Communication Guide 114 Image 7 2 InternetBridge NT wired internet connection...