IGS-NT Communication Guide
132
9.2.5 Modbus communication
via IB-NT
Modbus communication needs to be enabled in settings via IB-NT config.
Modbus is available as Modbus TCP or Modbus RTU over RS485.
Note:
For more information regarding IB-NT please see documentation
9.3 Modbus Protocol Description
9.3.1 Modbus TCP
Direct connection:
ETH
Port 502
Bridge connection:
IB-NT
Transfer mode TCP/IP
Function codes
3 (Read Multiple Registers)
6 (Write Single Register)
10 (Command)
16 (Write Multiple Registers)
The response to an incoming message depends on the network performace and on the controller
configuration. Typical response time is 25 ms.
Connection timeout is set to 15 seconds. If no message comes within the timeout then controller close the
connection.
Note:
Data structure is the same as Modbus RTU. Modbus TCP adds 6 bytes header before data. CRC
calculation is not used in Modbus TCP.
Summary of Contents for Inteli Mains NT BaseBox
Page 12: ...IGS NT Communication Guide 12 2 1 IG IS IM NTC BB Communications...
Page 13: ...IGS NT Communication Guide 13 2 2 IG IS IM NTC BB Terminals...
Page 14: ...IGS NT Communication Guide 14 2 3 IG IS IM NTC BB Peripheral modules...
Page 15: ...IGS NT Communication Guide 15 2 4 IG IS IM NTC BB Jumpers settings...
Page 16: ...IGS NT Communication Guide 16 2 5 IG IM NT BB Communication...
Page 17: ...IGS NT Communication Guide 17 2 6 IG IM NT BB Terminal...
Page 18: ...IGS NT Communication Guide 18 2 7 IG IM NT BB Peripheral modules...
Page 19: ...IGS NT Communication Guide 19 2 8 IG IM NT BB Jumper settings...
Page 20: ...IGS NT Communication Guide 20 2 9 IG NT Communications Terminals...
Page 22: ...IGS NT Communication Guide 22 2 11 IM NT Communications Terminals...
Page 23: ...IGS NT Communication Guide 23 2 12 IS NT BB Communications Terminals...
Page 65: ...IGS NT Communication Guide 65...
Page 114: ...IGS NT Communication Guide 114 Image 7 2 InternetBridge NT wired internet connection...