IGS-NT Communication Guide
103
7.4.11 Remote Switch 1-8 – Set (Remote Control 1-8)
Request:
01 10 18 D6 00 03 06 00 20 00 00 00 1A 7C 9A
01
= controller address
10
= Modbus command
18 D6
= Register address: Object for engine commands
(46359) – 40001 = 6358 DEC => 18D6 HEX
00 03
= number of Modbus registers
06
= data length in bytes (0001A)
00200000
= argument for RemoteSwitch1-8 (
001A
= command number (
), command = 26 DEC = 001A HEX
9A 7C
= CRC (write LSB MSB !)
Response:
01 10 18 D6 00 03 67 50
01
= Controller address
10
= Modbus command
18 D6
= Register address
00 03
= Release value, number of written Modbus registers
50 67
=
Summary of Contents for Inteli Mains NT BaseBox
Page 12: ...IGS NT Communication Guide 12 2 1 IG IS IM NTC BB Communications...
Page 13: ...IGS NT Communication Guide 13 2 2 IG IS IM NTC BB Terminals...
Page 14: ...IGS NT Communication Guide 14 2 3 IG IS IM NTC BB Peripheral modules...
Page 15: ...IGS NT Communication Guide 15 2 4 IG IS IM NTC BB Jumpers settings...
Page 16: ...IGS NT Communication Guide 16 2 5 IG IM NT BB Communication...
Page 17: ...IGS NT Communication Guide 17 2 6 IG IM NT BB Terminal...
Page 18: ...IGS NT Communication Guide 18 2 7 IG IM NT BB Peripheral modules...
Page 19: ...IGS NT Communication Guide 19 2 8 IG IM NT BB Jumper settings...
Page 20: ...IGS NT Communication Guide 20 2 9 IG NT Communications Terminals...
Page 22: ...IGS NT Communication Guide 22 2 11 IM NT Communications Terminals...
Page 23: ...IGS NT Communication Guide 23 2 12 IS NT BB Communications Terminals...
Page 65: ...IGS NT Communication Guide 65...
Page 114: ...IGS NT Communication Guide 114 Image 7 2 InternetBridge NT wired internet connection...