Group: Load shedding
Value: StatLdShed
Group
Load shedding
Units
-
Related FW
3.0
Description
The value indicates the current load shedding stage. 0 indicates that the load
shedding is not active. See the chapter
Load shedding
for more details.
Group: Analog CU
Value: UBat
Group
Analog CU
Units
V
Related FW
3.0
Description
Voltage at the controller power supply terminals.
Value: CPU Temp
Group
Analog CU
Units
ºC
Related FW
3.0
Description
Temperature inside the controller (on the CPU).
Value: D+
Group
Analog CU
Units
V
Related FW
3.0
Description
Voltage measured at the D+ terminal. If this voltage is > 80% of the
terminal is evaluated as active and the engine is evaluated as running. See also
the chapter
Start sequence
.
Value: AIN CU-1
Group
Analog CU
Units
configurable
Related FW
3.0
Description
This is the value of the analog input 1 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for oil pressure measurement.