background image

Before installation, check the baffle to be used and make sure the maximum permissible
length has not been exceeded, by means of a simple calculation:

1.

Establish the layout of the system of split flues, including accessories and outlet ter-
minals.

2.

Consult the table 5 and identify the losses in m

eq

 (equivalent metres) of every com-

ponent, according to the installation position.

3.

Check that the sum total of losses is less than or equal to the maximum permissible
length in table 4.

Table. 4 - Baffles for separate ducts

Table. 5 - Accessories

4. SERVICE AND MAINTENANCE

4.1 Adjustments

Gas conversion

The unit can operate on natural gas or LPG and is factory-set for use with one of the two
gases, as clearly shown on the packing and on the dataplate. Whenever a gas different
from that for which the unit is arranged has to be used, the special conversion kit will be
required, proceeding as follows:

1.

Replace the nozzles at the main burner, fitting the nozzles specified in the technical
data table in cap. 5, according to the type of gas used

2.

Modify the parameter for the type of gas:

put the water heater in standby mode

Press the on/off button detail 7 - fig. 1 for 20 seconds. the display shows “

b01

flashing.

press the DHW buttons details 1 and 2 - fig. 1 to set parameter 

00

 (for  use with

natural gas) or 

01

 (for use with LPG ).

Press the on/off button detail 7 - fig. 1 for 20 seconds.

the water heater will return to standby mode

3.

Adjust the minimum and maximum pressures at the burner (ref. relevant section),
setting the values given in the technical data table for the type of gas used

4.

Apply the sticker (contained in the conversion kit) near the dataplate as proof of the
conversion.

TEST mode activation

Draw enough domestic hot water to activate the DHW mode.

Press the buttons (details 1 and 2 - fig. 1) together for 5 seconds to activate the 

TEST

mode. The water heater will light at the maximum DHW power set as described in the
following section.

The DHW power will be shown on the display.

fig. 9 - TEST mode (DHW power = 100%)

Press the buttons (details 1 and 2 - fig. 1) to increase or decrease the power (Min.=0%,
Max.=100%).

To deactivate the TEST mode, press the buttons (details 1 and 2 - fig. 1) together for 5
seconds.

The TEST mode is automatically disabled in any case after 15 minutes or on stopping of
hot water drawing (if enough hot water was drawn to activate the DHW mode).

Pressure adjustment at the burner

Since this unit has flame modulation, there are two fixed pressure settings: minimum and
maximum, which must be those given in the technical data table according to the type of
gas.

Connect a suitable pressure gauge to the pressure point 

"B"

 downstream of the gas

valve.

Activate the TEST mode (see cap. 4.1).

Press the 

off button

 for 2 seconds to access the gas valve Calibration mode.

The card goes to the setting “

q02

”; displaying the actually saved value, by pressing

the DHW buttons .

If the pressure gauge reading is different from the nominal maximum pressure, pro-
ceed by increases/decreases of 1 or 2 units of parameter “

q02

” by pressing the

DHW buttons : the value is stored after each modification;  wait 10 seconds for the
pressure to stabilise.

Press the 

off button

 (ref. 7 - fig. 1).

The card goes to the setting “

q01

”; displaying the actually saved value, by pressing

the DHW buttons .

If the pressure gauge reading is different from the nominal minimum pressure, pro-
ceed by increases/decreases of 1 or 2 units of parameter "q01" by pressing the
DHW buttons : the value is stored after each modification; wait 10 seconds for the
pressure to stabilise.

Recheck both adjustments by pressing the Off button and adjust them if necessary
by repeating the above procedure.

Press the 

off button

 for 2 seconds to return to the TEST mode.

Deactivate the TEST mode (see cap. 4.1).

Disconnect the pressure gauge.

DHW power adjustment

To adjust the heating power, switch the unit to TEST mode (see sec. 4.1). Press the but-
tons detail 3 - fig. 1 to increase or decrease the power (Min. = 00 - Max. = 100). Press
the 

reset

 button within 5 seconds and the max. power will remain that just set. Exit the

TEST mode (see sec. 4.1).

S

UPREME E TS

Max. permissible length

Model

Length

S

UPREME

 11

65 m

eq

S

UPREME

 14

55 m

eq

S

UPREME

 17

45 m

eq

Baffle to use

Model

Length

Baffle

S

UPREME

 11

0 - 35 m

eq

Ø 43

35 - 65 m

eq

No baffle

S

UPREME

 14

0 - 30 m

eq

Ø 50

30 - 55 m

eq

No baffle

S

UPREME

 17

0 - 25 m

eq

Ø 50

25 - 45 m

eq

No baffle

Losses in m

eq

Air

inlet

Fume exhaust

Vertical

Horizontal

Ø 80

PIPE

0.5 m M/F

1KWMA38A

0.5

0.5

1.0

1 m M/F

1KWMA83A

1.0

1.0

2.0

2 m M/F

1KWMA06K

2.0

2.0

4.0

BEND

45° F/F

1KWMA01K

1.2

2.2

45° M/F

1KWMA65A

1.2

2.2

90° F/F

1KWMA02K

2.0

3.0

90° M/F

1KWMA82A

1.5

2.5

90° M/F + Test point

1KWMA70U

1.5

2.5

PIPE SECTION

with test point

1KWMA16U

0.2

0.2

for condensate drain

1KWMA55U

-

3.0

TEE

for condensate drain

1KWMA05K

-

7.0

TERMINAL

air, wall

1KWMA85A

2.0

-

fumes, wall with antiwind

1KWMA86A

-

5.0

FLUE

Split air/fumes 80/80

1KWMA84U

-

12.0

Fume outlet only Ø80

1K
1KWMA86U

-

4.0

fig. 10 - Gas valve

A

 - Upstream pressure point

B

 - Downstream pressure point

I

 - Gas valve electrical connection

R

 - Gas outlet

S

 - Gas inlet

fig. 11 - Gas valve connection

TYPE SGV100
Pi max 65 mbar
24 Vdc - class B+A

reset

R

B

I

A

S

~ 65

Ω

~ 24

Ω

SUPREME  E TS

4

EN

Summary of Contents for supreme e ts

Page 1: ...SUPREME E TS 195 200 118 40 50 50 27 C B D E Modello 11 E TS 14 E TS 17 E TS A mm 295 335 375 C D B A 595 E mm 210 250 290 EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE ...

Page 2: ...ing operation During a DHW demand generated by drawing domestic hot water the display detail 11 fig 1 shows the actual DHW outlet temperature Fault In case of a fault see cap 4 4 the display detail 11 fig 1 shows the fault code and during safety standby times the messages d3 and d4 2 3 Lighting and turning off Connection to the power supply During the first 5 seconds the display shows the card sof...

Page 3: ...with all the Cny flue configurations given on the dataplate Some configurations may be expressly limited or not permitted by law standards or local reg ulations Before installation check and carefully follow the instructions Also comply with the instructions on the positioning of wall and or roof terminals and the minimum distanc es from windows walls ventilation openings etc Baffles Unit operatio...

Page 4: ... and maximum which must be those given in the technical data table according to the type of gas Connect a suitable pressure gauge to the pressure point B downstream of the gas valve Activate the TEST mode see cap 4 1 Press the off button for 2 seconds to access the gas valve Calibration mode The card goes to the setting q02 displaying the actually saved value by pressing the DHW buttons If the pre...

Page 5: ...ult code Fault Possible cause Cure A01 No burner ignition No gas Check the regular gas flow to the water heater and that the air has been eliminated from the pipes Ignition detection electrode fault Check the wiring of the electrode and that it is correctly positioned and free of any deposits Faulty gas valve Check gas valve and replace it if necessary Gas valve wiring disconnected Check the wirin...

Page 6: ...tput kW 19 2 23 9 29 2 Min heat output kW 7 1 8 8 10 7 Pmax efficiency 88 5 88 7 88 9 Burner nozzles G20 no x Ø 10 x 1 25 12 x 1 25 14 x 1 25 Gas supply pressure G20 mbar 20 0 20 0 20 0 Max gas pressure at burner mbar 13 0 13 0 15 0 Min gas pressure at burner mbar 2 0 2 0 2 0 Max gas delivery G20 m3 h 2 30 2 85 3 48 Min gas delivery G20 m3 h 0 88 1 10 1 33 Burner nozzles G31 no x Ø 10 x 0 77 12 x ...

Page 7: ...5 4 Wiring diagram fig 15 Electrical circuit 81 1kW L N 230V 50 Hz 16 N L ABM02 73 R1 R2 R3 R4 288 T T 344 4 3 2 1 44 38 SUPREME E TS 7 EN ...

Page 8: ... p A Address Via Ritonda 78 a 37047 San Bonifacio VR Italy declares that this unit complies with the following EU directives Gas Appliance Directive 2009 142 Low Voltage Directive 73 23 amended by 93 68 Electromagnetic Compatibility Directive 89 336 amended by 93 68 President and Legal Representative Cav del Lavoro Dante Ferroli ...

Reviews: