background image

4.2 Start- up

Before lighting the water heater

Check the tightness of the gas system.

Fill the water system and make sure all air contained in the water heater and system
has been vented .

Make sure there are no water leaks in the system or unit.

Check correct connection of the electrical system and efficiency of the earthing sys-
tem.

Make sure the gas pressure value for heating is that required .

Make sure there are no flammable liquids or materials in the immediate vicinity of
the water heater.

Checks during operation

Switch the unit on.

Make sure the fuel circuit and water systems are tight.

Check the efficiency of the flue and air/fume ducts while the water heater is working.

Make sure the gas valve modulates correctly in the heating and hot water production
stages.

Check proper lighting of the water heater by doing several tests, turning it on and off
with the room thermostat or remote control.

Make sure the fuel consumption indicated on the meter matches that given in the
technical data table on cap. 5.

4.3 Maintenance

Periodical check

To ensure correct operation of the unit over time, have qualified personnel carry out a
yearly check, providing for the following:

The control and safety devices (gas valve, flowmeter, etc.) must work properly.

The fume exhaust circuit must be perfectly efficient.

The air/fume terminal and ducts must be free of obstructions and leaks

The burner and exchanger must be clean and free of deposits. For cleaning, do not
use chemical products or wire brushes.

The electrode must be properly positioned and free of scale.

fig. 12 - Electrode positioning

The gas and water systems must be tight.

The gas flow and pressure must correspond to that given in the respective tables.

4.4 Troubleshooting

Diagnostics

The water heater has an advanced self-diagnosis system. In case of a fault in the unit,
the display will flash together with the fault symbol (detail 11 - fig. 1) indicating the fault
code.

There are faults that cause permanent shutdown (marked with the letter "

A

"): to restore

operation just press the RESET button (detail 6 - fig. 1) for 1 second or RESET on the
optional remote timer control if installed; if the water heater fails to restart, it is necessary
to eliminate the fault .

Other faults (marked with the letter “

F

”) cause temporary shutdowns that are automati-

cally reset as soon as the value returns within the water heater's normal working range

List of faults

Table. 6

±

 0,5

=

=

Fault
code

Fault

Possible cause

Cure

      A01

No burner ignition

No gas

Check the regular gas flow to the 
water heater and that the air has been 
eliminated from the pipes

Ignition/detection  electrode fault

Check the wiring of the electrode and 
that it is correctly positioned and free 
of any deposits

Faulty gas valve

Check gas valve and replace it if 
necessary

Gas valve wiring disconnected

Check the wiring

Ignition power too low

Adjust the ignition  power

A02

Flame present signal with 
burner off

Electrode fault

Check the ionisation electrode wiring

Card fault

Check the card

A03

Overtemperature 
protection activation

DHW sensor damaged

Check the correct positioning and 
operation of the DHW sensor

No water circulation

Check the flowswitch

F04

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

F05

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

Fan fault

Wiring disconnected

Check the wiring

Faulty fan

Check the fan

Card fault

Check the card

A06

No flame after the ignition 
phase

Low pressure in the gas system

Check the gas pressure

Burner minimum pressure setting

Check the pressures

F07

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

A09

Gas valve fault

Wiring disconnected

Check the wiring

Faulty gas valve

Check the gas valve and replace it if 
necessary

F10

DHW sensor 1 fault

Sensor damaged

Check the wiring or replace the 
sensor

Wiring shorted

Wiring disconnected

F14

DHW sensor 2 fault

Sensor damaged

Check the wiring or replace the 
sensor

Wiring shorted

Wiring disconnected

A16

Gas valve fault

Wiring disconnected

Check the wiring

Faulty gas valve

Check the gas valve and replace it if 
necessary

F20

Combustion control fault

Fan fault

Check the fan and fan wiring

Wrong baffle

Check the baffle and replace it if 
necessary

Flue obstructed or not correctly 
sized

Check the flue

A21

Poor combustion fault

Fault F20 generated 6 times in the 
last 10 minutes

See fault F20

F34

Supply voltage under 180V. Electric mains trouble

Check the electrical system

F35

Faulty mains frequency

Electric mains trouble

Check the electrical system

A41

Sensor positioning

DHW sensor disconnected from 
pipe

Check the correct positioning and 
operation of the sensor

F42

DHW sensor fault

Sensor damaged

Replace the sensor

F50

Gas valve fault

Modulating Operator wiring 
disconnected

Check the wiring

Faulty gas valve

Check the gas valve and replace it if 
necessary

A51

Poor combustion fault

Inlet/exhaust flue obstruction

Check the flue

SUPREME  E TS

5

 

EN

Summary of Contents for supreme e ts

Page 1: ...SUPREME E TS 195 200 118 40 50 50 27 C B D E Modello 11 E TS 14 E TS 17 E TS A mm 295 335 375 C D B A 595 E mm 210 250 290 EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE ...

Page 2: ...ing operation During a DHW demand generated by drawing domestic hot water the display detail 11 fig 1 shows the actual DHW outlet temperature Fault In case of a fault see cap 4 4 the display detail 11 fig 1 shows the fault code and during safety standby times the messages d3 and d4 2 3 Lighting and turning off Connection to the power supply During the first 5 seconds the display shows the card sof...

Page 3: ...with all the Cny flue configurations given on the dataplate Some configurations may be expressly limited or not permitted by law standards or local reg ulations Before installation check and carefully follow the instructions Also comply with the instructions on the positioning of wall and or roof terminals and the minimum distanc es from windows walls ventilation openings etc Baffles Unit operatio...

Page 4: ... and maximum which must be those given in the technical data table according to the type of gas Connect a suitable pressure gauge to the pressure point B downstream of the gas valve Activate the TEST mode see cap 4 1 Press the off button for 2 seconds to access the gas valve Calibration mode The card goes to the setting q02 displaying the actually saved value by pressing the DHW buttons If the pre...

Page 5: ...ult code Fault Possible cause Cure A01 No burner ignition No gas Check the regular gas flow to the water heater and that the air has been eliminated from the pipes Ignition detection electrode fault Check the wiring of the electrode and that it is correctly positioned and free of any deposits Faulty gas valve Check gas valve and replace it if necessary Gas valve wiring disconnected Check the wirin...

Page 6: ...tput kW 19 2 23 9 29 2 Min heat output kW 7 1 8 8 10 7 Pmax efficiency 88 5 88 7 88 9 Burner nozzles G20 no x Ø 10 x 1 25 12 x 1 25 14 x 1 25 Gas supply pressure G20 mbar 20 0 20 0 20 0 Max gas pressure at burner mbar 13 0 13 0 15 0 Min gas pressure at burner mbar 2 0 2 0 2 0 Max gas delivery G20 m3 h 2 30 2 85 3 48 Min gas delivery G20 m3 h 0 88 1 10 1 33 Burner nozzles G31 no x Ø 10 x 0 77 12 x ...

Page 7: ...5 4 Wiring diagram fig 15 Electrical circuit 81 1kW L N 230V 50 Hz 16 N L ABM02 73 R1 R2 R3 R4 288 T T 344 4 3 2 1 44 38 SUPREME E TS 7 EN ...

Page 8: ... p A Address Via Ritonda 78 a 37047 San Bonifacio VR Italy declares that this unit complies with the following EU directives Gas Appliance Directive 2009 142 Low Voltage Directive 73 23 amended by 93 68 Electromagnetic Compatibility Directive 89 336 amended by 93 68 President and Legal Representative Cav del Lavoro Dante Ferroli ...

Reviews: