10. ADVANCED MENU
+ +
- Press simultaneously + + during 5 seconds.
- By mean of or the values can be changed.
- Press for validation.
- The parameters sequence is:
it
TYPE
SYSTEM REACTION
FAC-
TORY
SET-
TING
1
nc
no
Select the operation MODE as a con-
ventional pressure switch (nc = norma-
lly closed) or reverse (no = normally
open). *
see remark 3
nc
2
E00 E01/02
(Only Switchmatic2).
Select the operation mode Individual
(E00) or Master/Slave (E01/E02) in
case of be assembled in groups of two
pumps.
E00
2.1
d.05
d.1
(Only Switchmatic 2).
Sets the minimum gap between Pstart
1 and Pstart 2 and/or Pstop 1 and
Pstop 2.
d.05
3
ct0
ct9
Sets a time delay between 0 and 9
seconds to the start (is not available in
synchronized operation mode).
ct0
4
dt0
dt9
Sets a time delay between 0 and 9
seconds to the stop.
dt0
5
AE1
AE0/
AE2
(Only in Switchmatic 2)
Select
AE0
to dissable dry run alarm
by current consumption. To have a dry
run protection, the minimum pressure
value must be set.
Select
AE1
to enable dry run alarm
with auto-learning mode. In this mode,
the SW2 will learn the real consump-
tion of the pump.
Select
AE2
to enable dry run alarm
without auto-learning mode. In this
case, when the pump consumes a 40%
less of the value set as rated current,
the dry run alarm will appear.
6
Ar0
Ar1
Activation of the automatic restore
system ART (Ar1) o disable (Ar0).
Ar0
7
P0.0
Px.x
It allows setting a minimum operating
pressure under which the device would
determine dry-running operation. It is
very usefull in the basic model SWIT-
CHMATIC where there is no reading of
current intensity drawn. See Note 2.
0 bar
0 psi
7.1
t05
t99
Set the time period between 5 and 99
seconds below the minimum operating
pressure that will be considered a dry-
running operation.
20”
8
c10
c30
It allows setting a % of nominal current
above which the device will activate
the overcurrent protection.
c20
9
tE0
tE1
tE2
It manages the external inputs of the
in-out auxiliary circuit (on request).
tE0
: means disabled.
tE1
: minimum level contact input. It
would trigger alarm A21.
tE2
: external input. It allows to acti-
vate/deactivate the device by means
of an external contact, for example a
timer. If tE2 is enabled and the external
contact deactivates the equipment, the
display shows “
EL-
”
tE0
9.1
co1
co0
Only in case of tE1 activated:
co1: nc (normally closed contact).
co0: no (normally open contact)
co1
10
H00
H99
Anti-flooding configuration.
If activated, it stops the pump after
programmed time (in hours) of conti-
nuous operation.
Disabled (H00), 1 hour (H01) ... 24
hours (H24).
H00
11
r
rS1
If we change rS0 to rS1 and push EN-
TER default values are restored.
rS0
Remark 2:
Basic SWITCHMATIC 1/3 can only detect dry-running
operation through the minimum pressure. This means that
plumber must determine the water column of the installa-
tion, the start pressure of the pump and place the minimum
pressure below the start pressure.
It can also occur that pumping system is running out of its
curve so that the pump is unable to provide the minimum
pressure because the flow requirement is excessive. In this
case SWITCHMATIC 1/3 would activate a false dry-running
alarm.
If these concepts are not clear, it is preferable not configure
this protection or install the SWITCHMATIC 2 with accurate
and easy setting of dry-run detection.
Remark 3:
By choosing “no” (normally open) it will operate as an auxi-
liary pressure control element in the suction of the pump. It
will restart when the suction pressure reaches the configu
-
red PStart.
Example:
- PStop:
0,9 bar
-
PStart:
1,2
bar
11. SYNCHRONISATION (
ONLY FOR SWITCHMATIC 2
)
SWITCHMATIC 2 can be synchronized to another unit SWITCH-
MATIC 2 managing and protecting 2 pumps operating in cascade
with alternated starting sequence. Next steps must be followed:
1. GO TO ADVANCED MENU: + +
- In
step 2
: select E01 in a unit (this one will be the master) and
select E02 in the other unit (this one will be the slave).
- In
step 3
: select
identical
parameters of gap between pressu-
res d.XX. This is the difference beetween the starting pressure
of main and auxiliary pumps, it is also the difference beetween
stop pressures of both pumps.
2. Press repeatedly until exit the ADVANCED MENU.
3. SET
identical
cut-in and cut-out pressures in both units.
To optimize the synchronization, the minimum difference
between the start and stop pressures must be at least 1 bar.
4. Press in order to disable the units. Is displayed “OFF”.
5. Press
again in both units in order to activate the synchroni-
zation.
Remark 4: after 10 cycles the unit configured E01 will display
pressure and the unit configured E02 will display current in
Amps.