10. ADVANCED MENU  

 +   + 

- Press simultaneously  +   +   during 5 seconds.
- By mean of   or   the values can be changed.
- Press   for validation.

- The parameters sequence is:

it

TYPE

SYSTEM REACTION

FAC-

TORY 

SET-

TING

1

nc

no

Select the operation MODE as a con-

ventional pressure switch (nc = norma-

lly closed) or reverse (no = normally 

open). *

see remark 3

nc

2

E00 E01/02

(Only Switchmatic2).

Select the operation mode Individual 

(E00) or Master/Slave (E01/E02) in 

case of be assembled in groups of two 

pumps. 

E00

2.1

d.05

d.1

(Only Switchmatic 2).

Sets the minimum gap between Pstart 

1 and Pstart 2 and/or Pstop 1 and 

Pstop 2.

d.05

3

ct0

ct9

Sets a time delay between 0 and 9 

seconds to the start (is not available in 

synchronized operation mode).

ct0

4

dt0

dt9

Sets a time delay between 0 and 9 

seconds to the stop.

dt0

5

AE1

AE0/

AE2

(Only in Switchmatic 2)

Select 

AE0

 to dissable dry run alarm 

by current consumption. To have a dry 

run protection, the minimum pressure 

value must be set.

Select 

AE1

 to enable dry run alarm 

with auto-learning mode. In this mode, 

the SW2 will learn the real consump-

tion of the pump. 

Select 

AE2

 to enable dry run alarm 

without auto-learning mode. In this 

case, when the pump consumes a 40% 

less of the value set as rated current, 

the dry run alarm will appear.

6

Ar0

Ar1

Activation of the automatic restore 

system ART (Ar1) o disable (Ar0).

Ar0

7

P0.0

Px.x

It allows setting a minimum operating 

pressure under which the device would 

determine dry-running operation. It is 

very usefull in the basic model SWIT-

CHMATIC where there is no reading of 

current intensity drawn. See Note 2. 

 0 bar

0 psi

7.1

t05

t99

Set the time period between 5 and 99 

seconds below the minimum operating 

pressure that will be considered a dry-

running operation.

20”

8

c10

c30

It allows setting a % of nominal current 

above which the device will activate 

the overcurrent protection.

c20

9

tE0

tE1

tE2

It manages the external inputs of the 

in-out auxiliary circuit (on request).

tE0

: means disabled.

tE1

: minimum level contact input. It 

would trigger alarm A21.

tE2

: external input. It allows to acti-

vate/deactivate the device by means 

of an external contact, for example a 

timer. If tE2 is enabled and the external 

contact deactivates the equipment, the 

display shows “

EL-

tE0

9.1

co1

co0

Only in case of tE1 activated:

co1: nc (normally closed contact).

co0: no (normally open contact)

co1

10

H00

H99

Anti-flooding configuration. 

If activated, it stops the pump after 

programmed time (in hours) of conti-

nuous operation. 

Disabled (H00), 1 hour (H01) ... 24 

hours (H24).

H00

11

r

rS1

If we change rS0 to rS1 and push EN-

TER default values are restored.

rS0

Remark 2: 

Basic SWITCHMATIC 1/3 can only detect dry-running 

operation through the minimum pressure. This means that 

plumber must determine the water column of the installa-

tion, the start pressure of the pump and place the minimum 

pressure below the start pressure.

It can also occur that pumping system is running out of its 

curve so that the pump is unable to provide the minimum 

pressure because the flow requirement is excessive. In this 

case SWITCHMATIC 1/3 would activate a false dry-running 

alarm.

If these concepts are not clear, it is preferable not configure 

this protection or install the SWITCHMATIC 2 with accurate 

and easy setting of dry-run detection.

Remark 3:

By choosing “no” (normally open) it will operate as an auxi-

liary pressure control element in the suction of the pump. It 

will restart when the suction pressure reaches the configu

-

red PStart.

Example: 

- PStop:  

0,9 bar

  - 

PStart: 

 1,2 

bar

11. SYNCHRONISATION (

ONLY FOR SWITCHMATIC 2

)

SWITCHMATIC 2 can be synchronized to another unit SWITCH-

MATIC 2 managing and protecting 2 pumps operating in cascade 

with alternated starting sequence. Next steps must be followed:

1. GO TO ADVANCED MENU:   +   +   

- In 

step 2

: select E01 in a unit (this one will be the master) and 

select E02 in the other unit (this one will be the slave). 

- In 

step 3

: select 

identical

 parameters of gap between pressu-

res d.XX. This is the difference beetween the starting pressure 

of main and auxiliary pumps, it is also the difference beetween 

stop pressures of both pumps.

2. Press   repeatedly until exit the ADVANCED MENU.

3. SET 

identical

 cut-in and cut-out pressures in both units.

To  optimize  the  synchronization,  the  minimum  difference 

between the start and stop pressures must be at least 1 bar.

4. Press   in order to disable the units. Is displayed “OFF”.
5. Press 

 

again in both units in order to activate the synchroni-

zation.

Remark 4: after 10 cycles the unit configured E01 will display 

pressure and the unit configured E02 will display current in 

Amps.  

Summary of Contents for SWITCHMATIC 1

Page 1: ...HMATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus PROGRAMMATION AVANC E Risque de dommage au groupe de pression et ou l installation Risque de choc lectrique Risque pour les objets et ou les p...

Page 2: ...ssion d arr t 1 8 bar version plus 12 bar Diff rentiel maximal 7 5 bar version plus 11 5 bar Diff rentiel SW 0 5 bar SW2 synchro 1 bar Configuration usine marche arr t 3 4 bar Raccordement r seau hydr...

Page 3: ...elle est d tect rc2 2 1 r 01 r 99 Uniquement si l tape pr c dente l alarme de cycles rapides rc1 rc2 a t activ e alors nous pouvons s lectionner la dur e en secondes du p riode entre trois cons cutive...

Page 4: ...1 10 H00 H99 R glage de la minuterie d inondation La pompe s arr te si le temps pr c demment configur en minutes de fonctionnement ininterrompu est d pass D connect H00 1 minute H01 99 minutes H99 H00...

Page 5: ...DE PRESSION MINIMALE Appara t si en fonctionnement normal la ipression est inf rieure la pression minimale Px x pr d finie pendant la dur e txx pr alablement d fini dans le MENU AVANC Si tout moment...

Page 6: ...6 1x48 230Vac Vdc...

Page 7: ...V CLASSEMENT DES CONTACTS Tension de commutation maximale 230VAC 220VDC Puissance de commutation maximale 62 5VA 30W OUT SCH MA B ALIMENTATION LECTRIQUE ET MOTEUR 1x48 230Vac Vdc SW3 1x110 230Vac SW1...

Page 8: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAMME D...

Page 9: ...MATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus CONFIGURAZIONE AVANZATA Rischio di danno al gruppo di pressione o all impianto Rischio di scossa elettricha Rischio per le persone e o per gli...

Page 10: ...50 C Temperatura ambiente massima 60 C Pressione di messa in marcia 0 5 7 bar v plus 11 bar Pressione di fermata 1 8 bar v plus 12 bar Differenziale mass Pstop Pstart 7 5 bar v plus 11 5 bar Differen...

Page 11: ...eggia e il led START ON Mediante i tasti e si aggiusta la pressione di avvio da 0 5 a 7 bar version 11 bar Premere per validare 4 Inserire pressione d arresto Premere durante 3 secondi Visualizziamo n...

Page 12: ...terno disattiva la pompa il display visualizza EL tE0 9 1 co1 co0 Solo nel caso di tE1 attivato co1 nc contatto normalmente chiuso co0 no contatto normalmente aperto 10 H00 H99 Impostazione del timer...

Page 13: ...a definitiva A11 O MANCANZA D ACQUA PER PRESSIONE MINIMA Appare se in funzionamento nor male la pressione per sotto della pressione minima Px x previamente impostata durante il tempo txx previamente i...

Page 14: ...6 1x48 230Vac Vdc DIAGRAMMA A INDIVIDUALE GRUPPO SOLO SW2 SWITCHMATIC 1 2 SWITCHMATIC 3...

Page 15: ...1 C2 30mA L U N V CONTATTI RATING Mass tensione di commutazione 230VAC 220 VDC Mass potenza di commutazione 62 5VA 30W OUT SCHEMA B ALIMENTAZIONE E MOTORE 1x48 230Vac Vdc SW3 1x110 230Vac SW1 2 Premi...

Page 16: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAMMA D DIMENSIONI...

Page 17: ...1 SWITCHMATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus Riesgo para personas y o objetos Riesgo por choque el ctrico Riesgo de da o al grupo de presi n o a la instalaci n AJUSTES AVANZADOS...

Page 18: ...IP55 Temperatura m xima del agua 50 C Temperatura ambiente m xima 60 C Presi n de puesta en marcha 0 5 7 bar v plus 11 bar Presi n de de paro 1 8 bar v plus 12 bar Diferencial m xim Pstop Pstart 7 5...

Page 19: ...do y se ilumina el led START Mediante las teclas y se ajustar la presi n de puesta en marcha de 0 5 a 7 bar version 11 bar Pulsar para validar 4 Introducir presi n de paro Pulsar durante 3 segundos Vi...

Page 20: ...0 H99 Configuraci n del temporizador contra inundaci n Se detiene la bomba si se supera el tiempo en minutos previamente configurado de funcionamiento inin terrumpido Desconectado H00 1 minuto H01 99...

Page 21: ...R PRESI N M NIMA Aparece si en funcionamiento normal la presi n est por debajo de la presi n m ni ma Px x previamente establecida durante el tiempo txx previamente establecido en el MEN AVANZADO Si en...

Page 22: ...6 1x48 230Vac Vdc DIAGRAMA A INDIVIDUAL GRUPAL S LO SW2 SWITCHMATIC 1 2 SWITCHMATIC 3 USO OBLIGATORIO DE TANQUE HIDRONEUM TICO...

Page 23: ...SW1 2 SW3 SW1 2 SW3 C1 C2 C1 C2 30mA 1x48 230Vac Vdc SW3 1x110 230Vac SW1 2 L U N V Presione para liberar Cables 2 max 1 5 mm 2 min 0 2 mm CLASIFICACI N DE CONTACTOS Max Voltaje de conmutaci n 230VAC...

Page 24: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAMA D DIMENSIONES...

Page 25: ...1 SWITCHMATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus ADVANCED SETTINGS Risk of damaging the pressure assemblies and or the plant Risk by electric shock Risk for people and or objects...

Page 26: ...11 5 bar Minimum diff Pstop Pstart SW 0 5 bar SW2 synchro 1 bar Factory setting start stop 3 4 bar Hydraulic inlet G1 4 Fem NPT 1 4 Fem Net weight without cables 0 3 kg 5 HYDRAULIC INSTALLATION diagra...

Page 27: ...d on screen LED START lights up and display is flashing By mean of and is adjusted the start pressure from 0 5 to 7 bar version 11 bar Press for validation 4 Set the cut out stop pressure Press during...

Page 28: ...tivates the equipment the display shows EL tE0 9 1 co1 co0 Only in case of tE1 activated co1 nc normally closed contact co0 no normally open contact co1 10 H00 H99 Anti flooding configuration If activ...

Page 29: ...s after 24 h we find a definitive alarm A11 O DRY RUN NING BY MINIMUM PRESSURE Is displayed during normal operation if the pressure is below the minimum pressure Px x previously set during a period tx...

Page 30: ...6 1x48 230Vac Vdc DIAGRAM A INDIVIDUAL SYSTEM ONLY SW2 SWITCHMATIC 1 2 SWITCHMATIC 3 MANDATORY USE OF PRESSURE TANK MANDATORY USE OF PRESSURE TANK MANDATORY USE OF PRESSURE TANK...

Page 31: ...W3 C1 C2 C1 C2 30mA L U N V CONTACTS RATING Max switching voltage 230VAC 220 VDC Max switching power 62 5VA 30W OUT DIAGRAM B POWER SUPPLY AND MOTOR 1x48 230Vac Vdc SW3 1x110 230Vac SW1 2 Press to rel...

Page 32: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAM D DIMENSIONS...

Reviews: