
Electrovalves circuit identification
Block this tube
To the pump input are connected 2 tubes, one goes to
EV1
and
2
and the other one to
EV3
and
4
.
Make the test, bending the tube that goes towards
EV 3
and
4
as shown in the image.
If after blocking the tube the vacuum loss persists, proceed replacing the CPU, since possibly the
vacuum sensor is faulty.
Summary of Contents for Cooltech
Page 1: ...Cooltech SERVICE MANUAL Service Manual Cooltech V1 1 ...
Page 5: ... A4 01454 x2 A4 01453 A4 01454 A4 01455 A4 01455 A4 01455 x2 x2 x2 ...
Page 7: ...Packing layout A4 02266 A4 01389 x2 A4 01591 A4 01391 A4 01415 ...
Page 8: ......
Page 12: ...1 1 2 Vacuum system ...
Page 37: ...Power supply mounting screws For better access to the screws ...
Page 50: ...Power supply screws For better access to the screws ...