USER MANUAL :
DOCUMENT NAME
Sometimes it is necessary to re-calibrate the 4
values. This can be easily achieved by following the below procedure.
1.
Apply a fixed accurate 4mA source to the current loop interface.
2.
Dropdown the 'Calibrate Loop' menu and select 'Set 4mA Point'.
3.
Change the source current on the interface to an accurate 20mA.
4.
Dropdown the 'Calibrate Loop' menu and select the 'Set 20mA Point'.
5.
Change the loop current to any random value between 4mA and 20mA.
6.
Press the 'Get Current Setup' button and read back the settings.
7.
This random loop current should now display correctly in the 'General Details' box as 'Loop Current'.
8.
Disconnect loop current.
Upgrading firmware on the logger can be done through the Bluetooth interface. Newer versions of the software for each
type of device is embedded into the Cloudworks software so will not need an internet connection to collect the data.
When in Command Mode, press the 'Upgrade Firmware' button. The first thing the software will do is to determine the
current firmware version on the logger and see if
be prompted as such and given an option to re
you would like to try again.
Before continuing, the following prompt will flash on the screen.
Please do not at any stage interrupt the process while the firmware is downloading as this may leave the logger inoperable
and necessitate that it get sent back to the manufacturer for recovery.
Hardware Test
Setup Bluetooth
Calibrate Loop
Upgrade Firmware
Dropdown menu to activate various hardware tests. Selecting these options
will send the appropriate command to the logger and display the result in the
diagnostic screen.
Bluetoot
current Device Code for the logger. This makes it easier to select the correct
device when connecting to a Bluetooth interface. Should the Device Code not
appear on the list of devices when
(legacy devices), then pressing this button will reset the interface and correct
the naming system. This function can also be used to reset the Bluetooth
interface to the correct setup.
Used to calibrate the 4
The onboard firmware can be upgraded through the Bluetooth interface. The
process is explained in further detail below.
MANUAL : CDS541 CUMULUS PULSE LOGGER
NAME
CLASSIFICATION
DATE
PAGE
calibrate the 4-20mA loop to correct it or to re-calibrate for a completely different set of
values. This can be easily achieved by following the below procedure.
Apply a fixed accurate 4mA source to the current loop interface.
Dropdown the 'Calibrate Loop' menu and select 'Set 4mA Point'.
nt on the interface to an accurate 20mA.
Dropdown the 'Calibrate Loop' menu and select the 'Set 20mA Point'.
Change the loop current to any random value between 4mA and 20mA.
Press the 'Get Current Setup' button and read back the settings.
current should now display correctly in the 'General Details' box as 'Loop Current'.
Upgrading firmware on the logger can be done through the Bluetooth interface. Newer versions of the software for each
into the Cloudworks software so will not need an internet connection to collect the data.
When in Command Mode, press the 'Upgrade Firmware' button. The first thing the software will do is to determine the
current firmware version on the logger and see if there is an upgrade available. Should the firmware be up to date, you will
be prompted as such and given an option to re-flash the firmware. Re-flashing can happen if your last upgrade failed and
g prompt will flash on the screen.
Please do not at any stage interrupt the process while the firmware is downloading as this may leave the logger inoperable
and necessitate that it get sent back to the manufacturer for recovery.
Dropdown menu to activate various hardware tests. Selecting these options
will send the appropriate command to the logger and display the result in the
diagnostic screen.
Bluetooth interfaces are set to default 'Friendly Names' that include the
current Device Code for the logger. This makes it easier to select the correct
device when connecting to a Bluetooth interface. Should the Device Code not
appear on the list of devices when connecting to the Bluetooth interface
(legacy devices), then pressing this button will reset the interface and correct
the naming system. This function can also be used to reset the Bluetooth
interface to the correct setup.
Used to calibrate the 4-20mA. This is explained in further detail below.
The onboard firmware can be upgraded through the Bluetooth interface. The
process is explained in further detail below.
PAGE
for a completely different set of
current should now display correctly in the 'General Details' box as 'Loop Current'.
Upgrading firmware on the logger can be done through the Bluetooth interface. Newer versions of the software for each
into the Cloudworks software so will not need an internet connection to collect the data.
When in Command Mode, press the 'Upgrade Firmware' button. The first thing the software will do is to determine the
there is an upgrade available. Should the firmware be up to date, you will
flashing can happen if your last upgrade failed and
Please do not at any stage interrupt the process while the firmware is downloading as this may leave the logger inoperable
Dropdown menu to activate various hardware tests. Selecting these options
will send the appropriate command to the logger and display the result in the
h interfaces are set to default 'Friendly Names' that include the
current Device Code for the logger. This makes it easier to select the correct
device when connecting to a Bluetooth interface. Should the Device Code not
connecting to the Bluetooth interface
(legacy devices), then pressing this button will reset the interface and correct
the naming system. This function can also be used to reset the Bluetooth
This is explained in further detail below.
The onboard firmware can be upgraded through the Bluetooth interface. The