23
6 - START-UP
It is possible to limit the absorbed electric power with an external signal of 10 Vcc or 4-20 mA. The higher the signal is, the lower the
number of compressors available to meet the thermal need .
The parameter configuration is necessary.
MENU NUM
Parameter
name
meaning
thermoregulation-demandlimit 7
DmandLimitEn
Enables the function :
0=disabled , 1=by segnal, 2=by parameter
parameters-set-sensors
82
TypeDl
Type of signal : 0=0-10 V ; 1=4-20mA
It allows the automatic correction of the set-point, according to an
external signal of 4-20 mA or 0-10 vcc.
The working process is similar to the above mentioned process .
The parameter configuration is necessary .
°C
set point COMPENSATO
par 108
par 105
4 mA
20 mA
par11
MENU NUM
Parameter
name
Meaning
parameters
thermoregulation
waterreset
11
MaxCWRC
Max value of the summer WR correction
75 WaterReset
Water Reset enabling :
0=no ; 1=COOL only ; 2=HEAT only; 3=always
105
SWRMaxC
Summer MAX correction signal
108
SWRMinC
Summer MIN correction signal
parameters-set-sensors
83
TypeWR
Inlet signal type: 0=0-10V ; 1=4-20mA
6.12 DEMAND LIMIT
6.13 WATER RESET
It allows the automatic correction of the set-point according to the
external air temperature.
For example, the summertime with low external temperatures, it is
possible to have the internal comfort even with set-points higher
than the standard. The parameter configuration is necessary.
p4
p106
p107
Text °C
set COMPENSATO
MENU NUM
Parameter
name
Meaning
parameters
thermoregulation
compext
1 EnCompExt
External compensation enabling
0=no ; 1=COOL only ; 2=HEAT only; 3=always
4
MaxCExtC
Max. ext. compensation value of cooling
106
CextMaxC
Max. ext. temp. of cooling compensation
107
CextMinC
Min. ext. temp. of cooling compensation
parameters-set-sensors 9 ProbeText
It
enables ext. temp. probe: 0=yes ; 1=no
6.14 FRESH AIR TEMPERATURE PROBE
6.15 EXTERNAL AIR HUMIDITY PROBE
MENU NUM
Parameter
name
Meaning
parameters
thermoregulation
compext
4
MaxCExtC
Max. Summer correction value
110
HexMinC
Min. correction ext. enthalpy
111
HexMaxC
MAX. correction ext. enthalpy
parameters-set-sensors 23
ProbeURExt
Enables
external humidity probe: 1=YES / 0=NO
It allows the automatic correction of the set-point, according to external air enthalpy.
In the winter operation the correction is only on the temperature.
The operation process is similar to the above mentioned process. The parameter configuration is necessary.
Summary of Contents for WSH 100D
Page 9: ...9 4 WATER CONNECTIONS...
Page 12: ...12 WATER CONNECTIONS...
Page 14: ...14 5 ELECTRICAL CONNECTIONS 5 6 CONNECTIONS PERFORMER BY CUSTOMER...
Page 15: ...15 5 ELECTRICAL CONNECTIONS...
Page 16: ...16 5 ELECTRICAL CONNECTIONS...
Page 31: ...31 8 MAINTENANCE...
Page 46: ...46 NOTE...
Page 47: ...47...