5 - ELECTRICAL CONNECTIONS
5.1 PRELIMINARY INFORMATION
5.5 ELECTRIC LINES INLET
F.L.A. full load ampere
Full load current at max admissible conditions
F.L.I. Full load input
Full load power input
( at max. admissible condition )
serial
number
label
VOLTAGE
FLA (A)
FLI (kW)
The serial number label reports the unit specific electrical
data, included any electrical accessories .
The electrical data indicated in the technical bulletin and in the
manual refer to the standard unit, accessories excluded.
Refer to the electrical data report on the serial number label.
5.2 ELECTRICAL DATA
5.3 CONNECTIONS
1. refer to the unit electrical diagram (the number of the
diagram is shown on the serial number label)
2. verify that the network has characteristics conforming to
the data shown on the serial number label
3. Before starting work, verify that the sectioning device at
the start of the unit power line is open, blocked and
equipped with cartel warning
4. Primarily you have to realize the earthing connection
5. Shelter the cables using adequate measure fairleads
6. Before power the unit, make sure that all the protections
that were removed during the electrical connection work
have been restored.
5.4 SIGNALS / DATA LINES
Do not overpass the maximum power allowed, which varies,
according to the type of signal.
Lay the cables far from power cables or cables having a
different tension and that are able to emit electromagnetic
disturbances.
Do not lay the cable near devices which can generate
electromagnetic interferences.
Do not lay the cables parallel to other cables; cable crossings
are possible, only if laid at 90°.
Connect the screen to the ground, only if there aren’t
disturbances
Guarantee the continuity of the screen during the entire
extension of the cable.
Respect impendency, capacity and attenuation indications.
Fix the cables: if vacated may be subject to tearing.
The cable don't have to touch the compressor and the
refrigerant piping ( they reach high temparatures ).
The characteristics of the electrical lines must be determined
by specialized personnel able to design electrical installations;
moreover, the lines must be in conformity with regulations in
force.
The protection devices of the unit power line must be able to
stop the presumed short circuit current, whose value must be
determined in function of system features.
The power cables and the protection cable section must be
defined in accordance with the characteristics of the
protections adopted. All electrical operations should be
performed by trained personnel having the necessary
requirements by the regulations in force and being informed
about the risks relevant to these activities.
Operate in compliance with safety regulations in force .
Summary of Contents for WSH 100D
Page 9: ...9 4 WATER CONNECTIONS...
Page 12: ...12 WATER CONNECTIONS...
Page 14: ...14 5 ELECTRICAL CONNECTIONS 5 6 CONNECTIONS PERFORMER BY CUSTOMER...
Page 15: ...15 5 ELECTRICAL CONNECTIONS...
Page 16: ...16 5 ELECTRICAL CONNECTIONS...
Page 31: ...31 8 MAINTENANCE...
Page 46: ...46 NOTE...
Page 47: ...47...