42
WSAN-XES 18.2-35.2
M0SM40N17-04
Error code
Description
troubleshooting
F7
Reserved
1F9
radiator temperature sensor Tfin1
2F9
radiator temperature sensor Tfin2
1FA
Reserved
2FA
Reserved
Fb
pressure sensor
Detection begins 15 minutes after start-up, if a pressure
lower than 0.3 MPa is detected.
Not detected during defrosting.
Fd
suction temperature sensor
FE
recovery temperature sensor
1FF
fan A
2FF
fan B
3FF
fan C
FP
DIP switch for modular unit configuration error
C7
3 times PL
L0
module protection
L1
low voltage
L2
high voltage
L4
MCE error
L5
speed 0
L7
no phase
L8
variation of frequency higher than 15Hz
L9
difference of phase frequency higher than 15Hz
d0
Gate error (d0 and address alternatively
displayed every 10 sec)
dF
defrosting