29
WSAN-XES 18.2-35.2
M0SM40N17-04
In this case, disconnect the power supply and invert 2
phases on the machine power supply.
Do not let the compressor work for a long time with
opposite rotation: more than 2-3 of these abnormal start
-ups can damage it.
To ensure the rotation direction is correct, measure the
condensation and suction pressure.
The pressures must significantly differ: upon start-up,
the suction pressure decreases while the condensation
one increases.
Reduced load operation
The units are equipped with partialisation steps and so
can operate with reduced loads.
However, a constant and long operation with reduced
load with frequent compressor(s) stops and start-ups
can cause irreparable damages for the absence of oil
return.
The above-described operating conditions must be
considered outside the operating limits.
If the compressor breaks down due to operating in the
above-mentioned conditions, the warranty shall no
longer be valid and CLIVET spa
shall not accept any liability.
Periodically check the average operating times and
frequency of compressor start-ups: indicatively the
minimum thermal load must be such as to require a
compressor to operate for at least ten minutes.
If the average times are close to this limit, take the
proper corrective actions.
START-UP REPORT
dentifying the operating objective conditions is useful to
control the unit over time.
With unit at steady state, i.e. in stable and close-to-work
conditions, identify the following data :
Total voltages and absorptions with unit at full load
Absorptions of the different electric loads
(compressors, fans, pumps etc)
Temperatures and flows of the different fluids (water,
air) both in input and in output from the unit
Temperature and pressures on the characteristic
points of the refrigerating circuit (compressor
discharge, liquid, intake)
The measurements must be kept and made available
during maintenance interventions.
2014/68/UE PED DIRECTIVE
2014/68/UE PED DIRECTIVE gives instructions for
installers, users and maintenance technicians as well.
Refer to local regulations; briefly and as an example,
see the following:
Compulsory verification of the first installation:
only for units assembled on the installer’s building
site (for ex. Condensing c direct expansion
unit)
Certification of setting in service:
for all the units
Periodical verifications:
to be executed with the frequency indicated by the
Manufacturer (see the “maintenance inspections”
paragraph)