12
4 WATER CONNECTIONS
The unit must always be protected
from freeze.
Otherwise irreversible damage may
occur.
Minimum water flow
Maximum water flow
Risk of freeze
If the unit or the relative water connections can be subject to
temperatures close to 0°C:
x
Mix water with ethylene glycol, or
x
Safeguard the pipes with heating cables placed under the
insulation, or
x
Empty the system in cases of long non-use
Anti-freeze solutions
Consider that the use of anti-freeze solution determines an
increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not
corrosive) and compatible with the hydraulic circuit components.
Do not use different glicol mixture (i.e. ethylic with propylene).
Water flow-rate
The design water flow-rate must be:
x
inside the exchanger operating limits (see the TECHNICAL
INFORMATION chapter)
x
guaranteed also with variable system conditions (for example,
in systems where some circuits are bypassed in particular
situations)
If the system capacity is below the minimum flow, bypass the
system as indicated in the diagram.
If the system capacity exceeds the miaximum flow, bypass the
system as indicated in the diagram
Minimum system water content
Minimum system water contents are given in the ‘General
technical data’ section and they have to be satisfied to stop the
compressor from continuously switching on and off.
Water filter
Use filter with mesh pitch:
1,6 mm
Must be installed immediately in the water input of the unit,
in a position that is easily accessible for cleaning.
The filter never should be removed, this operation invalidates
the guaranty.
Summary of Contents for WDAT-iZ4
Page 1: ...R1234ze MANUAL FOR INSTALLATION USE AND MAINTENANCE WDAT iZ4 120 1 580 2 ...
Page 18: ...18 5 ELECTRICAL CONNECTIONS ...
Page 32: ...32 7 CONTROL ...
Page 33: ...33 7 CONTROL ...
Page 34: ...34 7 CONTROL ...
Page 35: ...35 7 CONTROL ...
Page 36: ...36 7 CONTROL ...
Page 37: ...37 7 CONTROL ...
Page 38: ...38 7 CONTROL ...
Page 39: ...39 7 CONTROL ...
Page 51: ...51 Compressor replacement 8 MAINTENANCE ...
Page 53: ...53 9 ANTIVIBRATION MOUNTS ...
Page 54: ...54 9 ANTIVIBRATION MOUNTS ...
Page 71: ......