AIR CONDENSER: SUGGESTED INSTALLATION
1/100
1/100
1/100
36
EN
i-ACCURATE i-AX - i-AW - i-AD - i-AT - i-AF
1/100
1/100
1/100
N.B.: Create traps as shown in the figure, making sure to fill them with oil when commissioning the system.
Fit a non-return valve at the unit outlet, on the gas outlet pipe.
The liquid piping must be protected against sunlight.
For two-circuit units (70-90-130-150), install an oil separator in the circuit with the ON/OFF compressor, for
lengths exceeding 50m, see the paragraph OIL SEPARATORS.
max 50 metres
discharge
air-conditioner
heat insulation
heat insulation
outlet
liquid
max 5
metres
air-conditioner
max 15
metres
max 3
metres
max 3
metres
heat insulation
air-conditioner