EN
i-ACCURATE i-AX - i-AW - i-AD - i-AT - i-AF
45
Values for individual component
FLI = Maximum power consumption
FLA = Max current
Vers.
Unit power supply
Humidifier modulating
Frame
Mod.
V/ph/Hz
V/ph/Hz
Qty.
FLI (kW)
FLA (A)
kg/h
2
12
230/1/50
230/1/50
1
2,25
9,8
3
2
18
400/3N/50
400/3/50
1
3,75
5,5
5
3
20
400/3N/50
400/3/50
1
3,75
5,5
5
3
29
400/3N/50
400/3/50
1
3,75
5,5
5
4
50
400/3N/50
400/3/50
1
3,75
5,5
5
5
70
400/3N/50
400/3/50
1
6
8,7
8
6
90
400/3N/50
400/3/50
1
6
8,7
8
7
130
400/3N/50
400/3/50
1
7,5
11
15
7
150
400/3N/50
400/3/50
1
7,5
11
15
Vers.
Unit power supply
Humidifier modulating
Frame
Mod.
V/ph/Hz
V/ph/Hz
Qty.
FLI (kW)
FLA (A)
kg/h
2
12
/
/
/
/
/
/
2
18
460/3/60
460/3/60
1
3,75
4,7
5
3
20
460/3/60
460/3/60
1
3,75
4,7
5
3
29
460/3/60
460/3/60
1
3,75
4,7
5
4
50
460/3/60
460/3/60
1
3,75
4,7
5
5
70
460/3/60
460/3/60
1
6
7,5
8
6
90
460/3/60
460/3/60
1
6
7,5
8
7
130
460/3/60
460/3/60
1
7,5
9,4
15
7
150
460/3/60
460/3/60
1
7,5
9,4
15
Vers.
Unit power supply
Humidifier modulating
Frame
Mod.
V/ph/Hz
V/ph/Hz
Qty.
FLI (kW)
FLA (A)
kg/h
2
12
/
/
/
/
/
/
2
18
380/3/60
380/3/60
1
3,55
5,7
4,7
3
20
380/3/60
380/3/60
1
3,55
5,7
4,7
3
29
380/3/60
380/3/60
1
3,55
5,7
4,7
4
50
380/3/60
380/3/60
1
3,55
5,7
4,7
5
70
380/3/60
380/3/60
1
5,73
9,1
7,6
6
90
380/3/60
380/3/60
1
5,73
9,1
7,6
7
130
380/3/60
380/3/60
1
7,11
11,4
14,2
7
150
380/3/60
380/3/60
1
7,11
11,4
14,2
POWER CONSUMPTION OF INDIVIDUAL COMPONENTS (HUMIDIFIER)
Summary of Contents for i-accurate