MINIMUM CROSS-SECTION OF THE POWER CABLES
ELECTRICAL SPECIFICATIONS
EN
i-ACCURATE i-AX - i-AW - i-AD - i-AT - i-AF
41
The cross-section of the power cable must be chosen according
to the length of the cable and the type of installation, based on
the maximum current input of the air-conditioner and so as to
prevent excessive voltage drops (the power supply voltage must
be between ± 10% of the rated value).
The following table shows the minimum recommended cross-sec-
tions for the power cables.
- A backup fuse should be fitted upstream of the power
line for short-circuit current up to 10 kA.
TOTAL UNIT POWER INPUT R410A
B = cooling only
R = cooling only + STD hearters
H = cooling only + humidifier
T = cooling only + STD h humidifier
Vers.
B
R
H
T
Frame
Mod.
V/ph/Hz
FLI (kW) FLA (A)
SA (A)
FLI (kW) FLA (A)
SA (A)
FLI (kW) FLA (A)
SA (A)
FLI (kW) FLA (A)
SA (A)
2
12
230/1/50
4,96
29,1
12
10,36
52,6
12
7,21
38,9
21
10,36
52,6
21
2
18
400/3N/50
11,06
19,4
20
19,06
54,2
20
14,81
24,9
26
19,06
54,2
26
3
20
400/3N/50
12,06
18,5
19
21,06
31,5
19
15,81
24,0
25
21,06
31,5
25
3
29
400/3N/50
18,66
28,7
20
27,66
41,7
20
22,41
34,2
26
27,66
41,7
26
4
50
400/3N/50
22,94
36,6
50
37,94
58,3
50
26,69
42,1
56
37,94
58,3
56
5
70
400/3N/50
30,26
53,9
162
36,36
55,9
162
36,26
62,6
162
36,36
62,6
162
6
90
400/3N/50
43,63
76,0
182
46,23
76,0
182
49,63
84,7
182
49,63
84,7
182
7
130
400/3N/50
52,18
93,0
190
52,38
93,0
190
59,68
104,0
190
59,68
104,0
190
7
150
400/3N/50
59,18
107,0
213
59,18
107,0
213
66,68
118,0
213
66,68
118,0
213
Vers.
B
R
H
T
Frame
Mod.
V/ph/Hz
FLI (kW) FLA (A)
SA (A)
FLI (kW) FLA (A)
SA (A)
FLI (kW) FLA (A)
SA (A)
FLI (kW) FLA (A)
SA (A)
2
12
460/3/60
/
/
/
/
/
/
/
/
/
/
/
/
2
18
460/3/60
11,16
17,4
20
19,3
27,6
20
14,91
22,1
25
19,26
27,6
25
3
20
460/3/60
12,16
16,5
19
21,2
27,8
19
15,91
21,2
24
21,16
27,8
24
3
29
460/3/60
19,16
25,8
20
28,2
37,1
20
22,91
30,5
25
28,16
37,1
25
4
50
460/3/60
22,94
36,6
50
37,9
55,5
50
26,69
41,3
55
37,94
55,5
55
5
70
460/3/60
30,79
51,9
162
36,4
52,5
162
36,79
59,4
162
36,79
59,4
162
6
90
460/3/60
42,25
69,0
166
46,2
69,0
166
48,25
76,5
166
48,25
76,5
166
7
130
460/3/60
40,81
67,0
166
52,4
75,2
166
48,31
76,4
166
52,38
76,4
166
7
150
460/3/60
42,4
69,0
166
52,4
75,2
166
49,9
78,4
166
52,38
78,4
166
Vers.
B
R
H
T
Frame
Mod.
V/ph/Hz
FLI (kW) FLA (A)
SA (A)
FLI (kW) FLA (A)
SA (A)
FLI (kW) FLA (A)
SA (A)
FLI (kW) FLA (A)
SA (A)
2
12
380/3/60
/
/
/
/
/
/
/
/
/
/
/
/
2
18
380/3/60
11,06
19,9
20
19,16
32,2
20
19,16
32,2
26
19,16
32,2
26
3
20
380/3/60
12,06
19,0
19
21,06
32,7
19
15,61
24,7
25
21,06
32,7
25
3
29
380/3/60
18,16
28,7
20
27,16
42,4
20
21,71
34,4
26
27,16
42,4
26
4
50
380/3/60
22,94
36,6
50
37,94
59,4
50
26,49
42,3
56
37,94
59,4
56
5
70
380/3/60
30,79
55,9
180
36,36
57,3
180
36,52
65,0
180
36,52
65,0
180
6
90
380/3/60
42,25
74,0
184
46,23
74,0
184
47,98
83,1
184
47,98
83,1
184
7
130
380/3/60
40,81
71,0
184
52,38
81,5
184
47,92
82,4
184
52,38
82,4
184
7
150
380/3/60
42,4
74,0
184
52,38
81,5
184
49,51
85,4
184
52,38
85,4
184