REV. FEBRUARY 19th 2014
CLIMA-FLEX S.A. DE C.V.
4.
ELECTRICAL DATA MODEL CLIV 230VAC/60 HZ/3PHASE
Unit Model
VOLT PH HZ
GAUGE
THW 75
°C
ELECTRICAL
PROTECTION (MCA1)
MOP
MCA
COMPRESSOR
FAN
MIN
MAX
LRA
OPERATING
AMPERAGE (1)
RLA
**
CANT.
RLA
HP
CLIV-ACC-036-A3S
220
3
60
8
20
13
19.70
12.90
73
7.50
12.9
1
2.77
1 1/4
CLIV-ACC-061-A3S
220
3
60
8
29
18
28.50
17.80
110
11.40
18.4
1
2.77
1 1/4
MCA
MAXIMUM CURRENT AMPACITY
MOP
MAXIMUM OPERATIONAL AMPACITY
LRA
LOCKED ROTOR AMPACITY
AMP OP
AMPACITY OF OPERATION
RLA
RATED LOAD AMPACITY
HP
HORSE POWER
Summary of Contents for CLIV SERIES
Page 1: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V CLIV SERIES Air cooled ...
Page 2: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V Installation Manual CLIV Series ...
Page 5: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V 1 2 CLIMA FLEX INSTALLATION DIAGRAM ...
Page 10: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V POWER DIAGRAM CLIV ACC 036 A3S CLIV ACC 061 A3S ...
Page 19: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V Operation Manual CLIV Series ...
Page 24: ...REV FEBRUARY 19th 2014 CLIMA FLEX S A DE C V Maintenance Manual CLIV Series ...