NPM Manual
2: Max. 24way outlets;
3: Three system signal indicator
RUN: Flashes when NPM work normally;
RLD: Lights when NPM unit receive command;
RND: Lights when command received not from this unit;
4: Indicator of network connection
5: Three connect ports
NET: For connecting master NPM to WAN, LAN or PC, when control via network;
SER: for connecting COM port of PC when control NPM via local RS-232;
LINK: When daisy chain multi NPM, this port for connecting serial port of next NPM;
6
、
T/H: For connecting 1 or 2pcs of temperature/humidity sensor;
7
、
SENSOR2: for connecting water, door open status sensor;
8
、
SENSOR1: for connecting smoke sensor;
9
、
OPTION: option switch for set up master and slave property, baud rate, etc.
10
、
RESET: reset button for restart NPM.
11: Choose group A or group B or group C outlets;
12: Choose certain outlet in a group(A/B/C);
13: On/off status of individual outlet, green color means switch on.
14: Display current and environment parameter, such as temperature, humidity,etc.
15: Display outlet No. chosen at present.
3. Hardware installation
3.1. Option Switch
1
: Choose master/slave property:
Option NO.1and option NO.2, for selecting master or slave features of NPM unit.
1OFF/2ON: NPM is master NPM, 1ON/2OFF NPM is slave NPM.
One master NPM max. can daisy chain 31pcs slave NPM.
2
: Choose baud rat
r setting baud rate: 3OF =19200BIT
,
3ON=9600BIT.
is 9600BIT
。
ddress, password of NPM;
ial value: password=12345678,
su
.
parameters: IP=192.168.0.178, Subnet
1, network
e:
Option NO.3 fo
F
Default baud rate of NPM
3
: Reset default value.
A
: Option No.1, No.2, No.3 for reset default a
Reset NPM default address and password init
address=65535;
Operate procedure:
1): Switch off power supply of total unit;
2): Set up option No.1, option No.2, option No.3 be on;
3): Switch on power supply of total unit, wait for 3 second, then switch off power
ply again, for 3 second;
p
4: Resume on/off status of option switch.
B
: Option No.4 for reset network default parameters of NPM
Reset NPM default network
mask=255.255.255.0
,
port=4001, baud rate=19200, data bit=8, stop bit=
setting password=88888;
Operate procedure:
Page 7 of 28