CONDENSATE REMOVAL

IO-DV090

IO-DV090

WWW.CLEANCOMFORT.COM

5

Lifting Condensate 

An optional condensate pump may be installed if a 

vertical lift is required to dispose of the condensate.  

The condensate pump can be ordered direct from  

your dealer. 

Condensate Pump Installation (optional) 

A condensate pump can be installed on the condensate 

drain line of the Clean Comfort DV090 dehumidifier if 

vertical lift is required to dispose of the condensate.  

Condensate is automatically pumped to a remote 

location when the water level in the condensate pump's 

reservoir rises to close the automatic float switch.  

In the event the pump fails and water rises too high in  

the reservoir a Safety Float Switch will become open.  

The leads from this switch should be installed in series 

with the yellow or blue field wires to prevent the pump 

from overflowing. If the yellow wire is in series with the 

Install the digital control in a central area of the home where 

it will sense the relative humidity accurately. 

I

 

CAUTION!

 

Do not install the control where it may not accurately 

 

sense the relative humidity such as near HVAC supply

 

registers, exterior doors, windows, water sources,  

 

or on an outside wall.  

 

The installer must supply the wiring between the DV090 

 

and the control. Be sure to safely route the control  

 

wiring to prevent damage during installation

 

I

 

CAUTION!

 

Do not cross wires when connecting the DV090 and the 

 

control or damage to the transformer may result. The 

 

remote controls of the DV090 are powered by a low  

 

voltage circuit (24VAC) and must NEVER contact or be 

 

connected to a high voltage circuit. 

 

The control wires leaving the DV090 and the control are 

numbered and color-coded to prevent confusion. Some of 

the control wires leaving the DV090 may not be used with 

certain control and should be left unconnected with wire 

nuts taped onto the stripped ends for safety. Be sure to 

consult the electrical schematic in this manual or inside  

the access panel of the DV090 before making control 

connections.

Condensate (Water) Removal 

The Clean Comfort DV090 dehumidifier generates  

condensate. Condensate drains by gravity via the drain 

port. Install a 3/4" male NPT adapter to the drain pan.  

It is necessary to assemble your own drain pipe assembly 

utilizing 3/4" PVC pipe to route the condensate to a drain. 

Pitch/grade of drain should be 1" per 10'. 

Take care when installing drain pipe to drain port of  

the DV090; Use an adjustable wrench to secure the  

drain port.

Figure 1: 

Trapping of Condensate Drain Line

 

I

 

CAUTION!

    

A trap in the drain line is required for the unit to drain  

    

properly. Local codes may require a trap. Use care to keep 

    

the pipe assembly as flat to the floor as possible. Kinks  

    

and/or humps will prevent proper drainage. 

When installing the drain hose make sure the feet are 

extended such that the dehumidifier is 2 1/2" off the 

ground. Then coil the drain hose under itself or position 

a spacer to lift the hose 1" off the ground after the hose 

has touched the ground. This procedure will create a 

trap that ensures your unit drains correctly. See the 

diagram below for further visual clarification.

Summary of Contents for DV090

Page 1: ...l the incoming air stream below its dew point This cooled and drier air is used to pre cool the incoming air stream resulting in increased overall efficiency After the pre cooling stage the processed air is reheated by passing through the condenser coil Fresh Air Ventilation Optional Fresh outdoor air may be ducted to the dehumidifier This provides fresh air to dilute indoor pollutants and repleni...

Page 2: ... Daikin North America LLC All rights reserved INTRODUCTION 1 SAFETY PRECAUTIONS 3 INTENDED APPLICATION 3 REGISTRATIONS 3 OPTIONAL PARTS LIST 3 SPECIFICATIONS 3 INSTALLATION 3 Installation Considerations 4 Power Accessibility 4 Space 4 Low Voltage Wiring 4 Back Draft Damper 4 Support Structure and Suspension 4 Electrical Requirements 4 Condensate Water Removal 5 Lifting Condensate 5 Condensate Pump...

Page 3: ...apacity 90 Pints Day 43 L Day Efficiency 5 3 pints kWhr 2 5 L kWhr Duct Connections 6 Round Inlet 10 Round Inlet 10 Round Outlet Air Filter Efficiency MERV 11 Standard 65 Efficient ASHRAE Dust Spot Test Size 14 X 14 x1 Power Cord 8 ft 2 4 m Drain Connection 3 4 Threaded FNPT Refrigerant Type R410a Refer to manufacturers label for more information Dimensions Unit Shipping Width 15 39 cm 18 47 cm He...

Page 4: ...o the unit Allow a minimum 15 clear ance to the side of the unit to allow for filter removal and replacement Low Voltage Wiring Unit location should be in an area where field wiring the remote controls low voltage to the unit will be possible Back Draft Damper It is recommended that a backdraft damper be used in the supply duct of the DV090 especially when con necting to the supply ducting system ...

Page 5: ...he remote controls of the DV090 are powered by a low voltage circuit 24VAC and must NEVER contact or be connected to a high voltage circuit The control wires leaving the DV090 and the control are numbered and color coded to prevent confusion Some of the control wires leaving the DV090 may not be used with certain control and should be left unconnected with wire nuts taped onto the stripped ends fo...

Page 6: ...collars to the DV090 Step 1 Attach 6 diameter fresh air ventilation damper if desired Safety Float Switch the DV090 and the dehumidifier will shut off If the blue wire is in series with the Safety Float Switch the compressor will turn off but the DV090 will continue to ventilate or circulate air as normal Contact your local electrician to install the safety float switch directly to the dehumidifie...

Page 7: ... for 90 flow option 180 Flow Attach the second 10 duct collar as you did the first Use six 8 screws provided Ducting for Dehumidification For the ideal installation draw air from the central part of the home and return it to the isolated areas of the home like the bedrooms den utility room or family room Be sure to utilize as many of these remote rooms as possible and not just one location The duc...

Page 8: ...performance positively or negatively depending upon the inside and outside air conditions The outside air duct should be connected to the 6 round collar on the front of the DV090 The amount of outside air can be restricted by the blade damper in the 6 collar Fresh Air Supply Air I CAUTION DO NOT draw air directly from the kitchen laundry or isolated basement You may draw air from a basement that i...

Page 9: ...If you are unsure of your ventilation air requirements or have need for higher air flows consult Technical Support by calling 1 855 239 2665 Figure 5 Attic Installation Installation in a Basement or Crawlspace with an Existing Forced Air HVAC System Crawlspace Installation Install a separate return to the DV090 in a central area of the home Optional Duct the supply from the DV090 to a 10 x 10 x 10...

Page 10: ...ventilation See Figure 6 Figure 6 Installation with no forced air HVAC system Ducting for High Efficiency Filtration The filter included with the DV090 is a very efficient MERV 11 media filter This filter should be checked every three months and changed every 6 12 months Quiet Installation Consider compression vibration and airflow noise during installation Use of flex duct and or vibration isolat...

Page 11: ...not used do not connect the white wire to the DVP 4034748 control or damage to the transformer may result I CAUTION DO NOT allow the yellow lead from the unit to contact the red lead or the white lead from the unit or damage to the transformers will result A 40VA transformer is wired between the red white lead and the yellow leads of the DV090 This low voltage power source powers the relay coils w...

Page 12: ...ty Range Accuracy 10 95 RH 5 Humidity Range Set Point 35 70 RH Auxiliary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 1 32 C 2 Size 4 95 L x 1 06 W x 4 19 H 12 6 cm L x 2 7 cm W x 10 6 cm H Major Operations Digital control of Relative Humidity Digital Set Point Fan Filter Operation Programmable Ventilation Timer Large easy to read backlit LCD display Easy interaction with air handler fa...

Page 13: ...ic for DV090 Wiring Schematic I WARNING Servicing the DV090 with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury and or property damage Call your HVAC contractor for servicing or repair of this equipment To replace the filter remove the filter door from the side of the DV090 dehumidifier by gently pulling it...

Page 14: ...ator and compresses it to a high pressure and temperature to repeat the process Troubleshooting Neither fan nor compressor running Dehumidification is being called for No fan call 1 Unit unplugged or no power to outlet 2 Humidity control set too high 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer Compressor is not running Dehumidificat...

Page 15: ...1 855 239 2665 Refrigerant Charging If the refrigerant charge is lost due to service or a leak a new charge must be accurately weighed in If any of the old charge is left in the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type Compressor Capacitor Replacement This compressor is equipped with a two terminal ...

Page 16: ...la tion at the correct times Motorized Ventilation Damper The motorized ventilation damper is controlled by a field supplied ventilation timer such as the Clean Comfort DVP 4034748 control The damper will open when the ventilation timer is activated to allow fresh air into the home through the 6 diameter fresh air inlet supply duct The motorized ventilation damper will remain closed when the venti...

Page 17: ...allasufficientlylongdrainhosetoconnect thedrainadaptorofthedehumidifiertothecondensate pumpreservoirusingfield suppliedfittings Step 6 Attachadrainhosetothecondensatepump androuteittoafloordrain Step 7 Use a level to ensure the dehumidifier is level before powering up the dehumidifier and the condensate pump Step 8 Plug in the condensate pump and the assembly is completed Annual inspection of a pr...

Page 18: ...nty A defect under the terms of this limited warranty shall not include problems resulting from Customer s or Customer s employees agents invitees or a third party s misuse improper installation improper design of any system in which the Product is included abuse lack of normal care failure to follow written instructions tampering improper repair or freezing corrosion acts of nature or other cause...

Page 19: ...IO DV090 WWW CLEANCOMFORT COM 19 Notes ...

Page 20: ...W CLEANCOMFORT COM IO DV090 2 14 Our continuing commitment to quality products may mean a change in specifications without notice 2014 DAIKIN NORTH AMERICA LLC Houston Texas USA Email info cleancomfort com 1 855 239 2665 ...

Reviews: