Operator's Manual: Model CB-1400
10-3
PROBLEM
POSSIBLE CAUSE
POSSIBLE ACTION(S)
Burner won’t run at all and
Green power light is NOT ON.
1.
Circuit breaker/main switch open.
2.
Fuse/breaker blown.
3.
Burner cable is damaged or not
plugged in properly.
1.
Close circuit breaker/switch.
2.
Electrician should check out
electrical system.
3.
Check burner cable.
Burner won’t run at all and
Green power light is ON.
1.
Oil primary control has shut down
on safety reset.
2.
Wall thermostat is not operating.
3.
Heater block is not heating up.
4.
F-120 proving switch has not
closed.
5.
Oil primary control terminals are
not wired correctly.
6.
Oil primary control is damaged.
7.
The High Limit Switch on the
Fan / Limit Control has activated.
1.
Follow the directions in Section 7
to reset the oil primary control.
2.
Check the wall thermostat and
thermostat cable.
3.
Feel the back of the burner; it
should be 140 degrees F. If the
heater block is NOT HOT: (a)
Wait 15 minutes for the heater
block to heat up and re-check the
back of the burner, and (b) Check
the block heater thermostat and
block heater element. Refer to
the wiring diagram and ladder
schematic in Appendix B.
4.
If the block is HOT: (a) Check the
red wire at the F-120 proving
switch for power. If there is NO
power at the red wire, refer to the
wiring diagram and ladder
schematic in Appendix B to
troubleshoot the circuit that
provides power to the proving
switch. (b) If there is power at the
red wire at the proving switch,
check for power at the black wire.
If there is NO power at the black
wire, replace the F-120 proving
switch.
5.
Check the oil primary control: (a)
Check that the “F” terminals are
NOT jumped. (b) Check that the
two yellow cad cell wires are
connected to the “F” terminals. (c)
Check that the two thermostat
wires are connected to the “T”
terminals.
6.
Replace oil primary control: (a)
Check voltage – it must be 115
volts.
7.
Refer to Appendix A for
instructions on the Fan / Limit
Control.
Troubleshooting Tables
Summary of Contents for CB-1400
Page 2: ......
Page 8: ......
Page 18: ...Operator sManual ModelCB 1400 1 10 ...
Page 62: ...Operator sManual ModelCB 1400 5 8 ...
Page 68: ...Operator sManual ModelCB 1400 7 2 ...
Page 84: ...Operator sManual ModelCB 1400 9 10 ...
Page 92: ...Operator sManual ModelCB 1400 10 8 ...
Page 108: ...Operator sManual ModelCB 1400 C 2 ...