Operator's Manual: Models CB-1750, CB-2500 & CB-3250
B-11
Model 40200/ 42230 CAD Cell Oil
Primary Control Data Sheet
• Oil pump bleed assist
up to 1 min.
• Serviceman Reset Protection
Latch-up after 3 consecutive lockouts
• Diagnostic LED’s
• 15-second TFI/ 30-second TFI
L2
L2 L2
LIMIT IN
120V, 60 HZ
LINE
HEAT-
ER
MOTOR
10FLA
60LRA
IGNITOR
500VA
VALVE
• Thermostat/aquastat compatible
• Improved SMC Technology
zero bleed voltage during standby
• Works well with generators
Insensitive to frequency changes
• Flame Stabilize
Model 40200/42230 diagnostic LED’s
– Amber OFF
– Amber ON
– Amber FLASHING
– Green OFF
– Green ON
– Green FLASHING
– Red OFF
– Red ON
– Red FLASHING
Installing and wiring
Warning
—
1. Always disconnect power source before wiring to avoid electrical shock or damage to the control. All wiring must comply with applicable codes and
ordinances.
2. Thermostat terminals (T–T) provide a current source. Never apply external power to these terminals under any circumstances.
Mounting
• The control may be mounted on a 4” x 4” junction box in any convenient location on the burner, furnace or wall. The location must not exceed the ambient
temperature limit, 140°F.
Wiring
• Wiring must comply with local and national electrical codes, and with the wiring diagram.
Field checks
1.
Safety timing (TFI) test
— Remove one cad cell wire (F-F). Start burner.
The control should lockout within the TFI time limit. Replace cad cell wire.
2.
Flame failure test
as described on the reverse side of this Data sheet. The control should recycle (restart after 65 seconds).
3. If control does not operate as described, check the wiring.
Start-up & operation
Do not start the burner if the combustion chamber
contains oil or oil vapor.
The amber LED
every 3 to 4 seconds & green LED will be on or blinking.
Power ON
Open all manual oil line valves. Close the line switch.
Self-test 1
The control performs a “boot-up” test to verify internal operation each time power is applied to the black wire. The amber LED turns
on and the test continues for about 5 seconds. If the test fails, the control turns the amber LED off and repeats this test sequence
until successful.
Stand-by
(No call for heat) If Self-test 1 is successful, amber LED turns off and control waits for heat call.
Call for heat
Set thermostat and limit to call for heat. Thermostat circuit must be closed and power coming to black wire from limit circuit.
Self-test 2
If a failure occurs in this self-check, the control won’t start and the amber LED blinks 1 second on, 4 seconds off, until serviced or the
problem clears. These failures include CAD cell seeing light, internal fault, or line voltage <90V. See service section.
Burner on
After the self-test, amber LED turns off. The ignitor starts, followed 2 seconds later by the motor.
Power input (from limit circuit)
120 VAC, 60 HZ, 10 VA
Motor load
10 FLA/ 60 LRA
Ignitor load
120 VAC, 60 HZ, 500 VA
Operating temperature limits
+32°F to +140°F
Storage temperature limits
-40°F to +185°F
Thermostat anticipator current
0.1 A, AC
Cad cell resistance
R < 1500 OHMS
Agencies
UL recognized (US & Canada)
C77009
Understanding the Oil Primary Control
Model 40200 / 42230 Cad Cell Oil Primary Control Data Sheet
Summary of Contents for CB 140
Page 2: ......
Page 8: ...TABLE OF CONTENTS APPENDIX C Furnace Service Record C 1 ...
Page 40: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 3 20 ...
Page 72: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 5 6 ...
Page 80: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 7 4 ...
Page 96: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 9 10 ...
Page 104: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 10 8 ...
Page 128: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 A 24 ...
Page 142: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 C 2 ...