SPECIFICATION 

 

MODEL 

 

CPI-500 

CPI-1000 

CAPACITY 

VA/W 500VA/300W 

1000VA/600W 

Nominal Voltage 

220~240VAC 

Input Voltage Range 

90~280VAC 

AC INPUT   

Nominal Frequency 

50Hz or 60Hz (Auto Detection) 

Voltage 

±

15% 

Frequency 

50/60Hz 

±

0.1Hz 

Waveform Modified 

Sine-wave 

Efficiency (AC to AC) 

> 95% 

OUTPUT 

Efficiency (DC to AC) 

> 80% 

BATTERY 

Nominal Voltage 

12Vdc 

24Vdc 

Charging Voltage 

13.7V 

27.4V 

Charging Current   

8A max. 

6A max. 

CHARGER 

Overcharging Protection 

14.5V 

29V 

TRANSFER  

Transfer Time 

8ms typical 

Line mode 

Green LED blinks or lights steadily 

Battery mode 

Yellow LED lights 

INDICATOR 

Overload/fault 

Red LED blinks or lights steadily 

Low Battery Voltage in 
battery mode 

Buzzing every 2 seconds 

Overload 

Buzzing every 0.5 second. 

AUDIBLE ALARM 

Fault Buzzing 

continuously 

ENVIRONMENT 

Temperature 

0 ~ 40°C 

Dimension (mm) DXWXH 

224x255x80 

 
PHYSICAL 

Net Weight (Kg) 

1.7 

 
 
 

Summary of Contents for CPI-1000 Series

Page 1: ...USER MANUAL CiTO Power INVERTERS Series CPI 500 CPI 1000...

Page 2: ...es must be rated for 75o C or higher and should be no less than 10AWG gauge The inner diameter of the copper ring terminal which is used to connect battery cables to Inverter DC terminals should be no...

Page 3: ...is connected to a wall socket utility power goes to connected equipment s and or charges the battery set via charging system In UPS mode Inverter automatically converts battery energy into AC power f...

Page 4: ...atically and works in mains mode or inverter mode according to input AC source s status When press this button again Inverter will turn off automatically Mains Mode LED The green LED will blink or lig...

Page 5: ...tor Three station Terminal Block 4 Output Receptacle s 5 Input Voltage Range Selector Input voltage range is defined in specification chapter and output voltage is the same as input voltage in mains m...

Page 6: ...inal Tighten the M5 nut Do not place anything between the flat part of battery terminal and the battery cable ring terminal or overheating may occur Figure 4 Battery Cable Connections to CPI 500 1000...

Page 7: ...otal output voltage This voltage MUST match the DC voltage requirements of the CiTO unit or damage may occur to both the CiTO unit and or the batteries z Parallel Connection Wiring batteries in parall...

Page 8: ...e is disconnected before attempting to connect AC power cables and load to Inverter Step 2 Connect the hot wire black brown of AC input cable to the HOT IN terminal Step 3 Connect the neutral wire whi...

Page 9: ...Voltage 12Vdc 24Vdc Charging Voltage 13 7V 27 4V Charging Current 8A max 6A max CHARGER Overcharging Protection 14 5V 29V TRANSFER Transfer Time 8ms typical Line mode Green LED blinks or lights stead...

Page 10: ...connection Mains normal but works in inverter mode Input protector is effective Reset the input protector Alarm buzzer beeps continuously Overload Verify that the load matches the capability specified...