Battery Connection 

Step 1- 

Pinch the bottom of DC input cover and Open it. See Figure 4.   

Step 2- 

Following battery polarity guide located near battery terminal. Place 

the battery cable ring terminal over Inverter’s battery terminal. 

Tighten the M5 nut.

 

Do not place anything between the flat part of 

battery terminal and the battery cable ring terminal, or overheating 

may occur. 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 4 Battery Cable Connections to CPI-500 / 1000 

 

Caution!

  DO NOT place 

anything between battery cable 

ring terminals and battery 

terminals. The terminal stud is 

not designed to carry current. 

Apply Anti-oxidant paste to 

terminals after terminals have 

been securely connected.

 

Summary of Contents for CPI-1000 Series

Page 1: ...USER MANUAL CiTO Power INVERTERS Series CPI 500 CPI 1000...

Page 2: ...es must be rated for 75o C or higher and should be no less than 10AWG gauge The inner diameter of the copper ring terminal which is used to connect battery cables to Inverter DC terminals should be no...

Page 3: ...is connected to a wall socket utility power goes to connected equipment s and or charges the battery set via charging system In UPS mode Inverter automatically converts battery energy into AC power f...

Page 4: ...atically and works in mains mode or inverter mode according to input AC source s status When press this button again Inverter will turn off automatically Mains Mode LED The green LED will blink or lig...

Page 5: ...tor Three station Terminal Block 4 Output Receptacle s 5 Input Voltage Range Selector Input voltage range is defined in specification chapter and output voltage is the same as input voltage in mains m...

Page 6: ...inal Tighten the M5 nut Do not place anything between the flat part of battery terminal and the battery cable ring terminal or overheating may occur Figure 4 Battery Cable Connections to CPI 500 1000...

Page 7: ...otal output voltage This voltage MUST match the DC voltage requirements of the CiTO unit or damage may occur to both the CiTO unit and or the batteries z Parallel Connection Wiring batteries in parall...

Page 8: ...e is disconnected before attempting to connect AC power cables and load to Inverter Step 2 Connect the hot wire black brown of AC input cable to the HOT IN terminal Step 3 Connect the neutral wire whi...

Page 9: ...Voltage 12Vdc 24Vdc Charging Voltage 13 7V 27 4V Charging Current 8A max 6A max CHARGER Overcharging Protection 14 5V 29V TRANSFER Transfer Time 8ms typical Line mode Green LED blinks or lights stead...