DRYER INSTALLATION WITH MULTIPLE EXHAUST
For
Exhaust
Duct
more
than
14
feet
and
2
elbows
equivalent
and
more
than
0.3
inches
static
pressure.
(See
illustration
on
next
page.)
1.
Make-up air from outside building may enter enclosure from top or side walls. Area of opening
should be equal to 4 to 6 times the sum of dryer duct areas. Provide 1 square foot (.1m²) for each
6 inches (15.24 cm) diameter; 2 square feet (.2m²) for each 8 inches (20.3 cm) diameter; and 4
square
feet
(.4m²)
for
each
12
inches
(30.5
cm)
diameter.
2.
Use constant diameter duct with area equal to the sum of dryer duct areas.
EXAMPLE: 6-8 inches (20 cm) diameter duct = 1-19.6 inches (49.8 cm) diameter duct in area.
Use 20 inches (50 cm) diameter duct or diameter to match tube-axial fan.
3.
Enclosure (plenum) with service door. This separates the dryer air from room comfort air. If
dryers use room air instead of outside air, the heat loss can be another 25 BTU/HR (6.3 kcal/hr)
for each cubic foot per minute (CFM) used.
4.
Zero inches clearance to combustible material allowed on sides and at points within 4 inches
(100 mm) of front on top.
5.
Heat loss into laundry room from dryer fronts
only is about 60 BTU/HR per square foot (15 kcal/
hr
per
0.1m²).
6.
Flange mounted, belt driven tube-axial fan. Fan must run when one or more dryers are
running.
See suggested Automatic Electrical Control Wiring Diagram on previous page. Must
meet
local
electrical
codes.
Fan
air
flow
(CFM)
(M³/min.)
is
equal
to
sum
of
dryer
air
flows,
but
static pressure (SP) is dependent on length of pipe and number of elbows.
7.
Barometric Bypass Damper—Adjust to
closed flutter position with all dryers and exhaust
fan running. Must be located within enclosure.
CAUTION:
Never install hot water heaters or other gas appliances in the same room as
dryers.
Never install cooling exhaust fans in the same room as dryers.
CAUTION:
Never exhaust dryers with other types of equipment.
Summary of Contents for L36TD30ME
Page 10: ...Page 10 S6162 BS MMC 010 12489...
Page 20: ...Page 20 S6162 BS MMC 010 12489 RECOMMENDED STEAM PIPING INSTALLATION ILLUSTRATION...
Page 40: ...Page 40 S6162 BS MMC 010 12489 BACK CHANNEL BOLTED ASSEMBLY TU10600...
Page 50: ...Page 50 S6162 BS MMC 010 12489...
Page 51: ...Page 51 S6162 BS MMC 010 12489...
Page 52: ...Page 52 S6162 BS MMC 010 12489...
Page 53: ...Page 53 S6162 BS MMC 010 12489...