A.1 Rack Mounting
The Cisco C880 Server (including peripheral devices) has been developed and its operation guaranteed with
the basic assumption that it is mounted in a rack. For safe use of a unit mounted in a rack, contact the
distributor where you purchased your product, or your sales representative.
When mounting the Cisco C880 Server products in a rack manufactured by another company, customers
need to confirm on their own responsibility that the rack meets the Cisco C880 Server product specifications
and requirements.
See
A.2.2 Requirements for mounting in
A.2 Rack Mounting Requirements
This section describes rack mounting requirements.
A.2.2 Requirements for mounting in a third party's rack
When mounting the Cisco C880 Server products in a rack manufactured by another company, customers
need to confirm on their own responsibility that the rack meets the Cisco C880 Server product specifications
and requirements.
TABLE A.1 Structural condition of rack
Number of Check
Term
Condition
Reference
Length of rack
Check1
Allowable spacing between
posts
685 to 790mm
(26.7 to 31.1 in.)
Check2
Length between front post and
rear cover
860mm(33.9 in.) or more
Check3
Length between front post and
front cover
60mm(2.4 in.) or more
Width of rack
Check4
distance between the left and
right posts (common to the
front and rear posts)
450mm(17.7 in.) or more
FIGURE A.2 Width
of rack
FIGURE A.3 Format
of rack posts
Check5
Distance between holes on the
left and right device mounting
posts (common to the front
and rear posts):
465mm(18.3 in) or more
(EIA standard)
FIGURE A.2 Width
of rack
FIGURE A.3 Format
of rack posts
Check6
Bracket installation space
There must not be interference thing
(post for reinforcement or option) in
the shaded portion of figure.
Format of rack
Check7
Pitch of hole
EIA standard, universal pitch
FIGURE A.3 Format
of rack posts
Check8
Format and size of hole
Length of each side of a square hole:
9x9(0.35 in.) to 10x10 mm (0.39 in.)
FIGURE A.3 Format
of rack posts
Check9
Cable takeout port
The cable can be taken out of the
bottom or rear.
Check10
Loading Carrying Capacity of
rack
Total weight must be less than
l
oading Carrying Capacity of rack.
Note
L
oading Carrying Capacity of rack
may change when anti-earthquake
measures are given.
-
Check11
Open area ratio of rack
Open area ratio of rack of front cover
and rear cover must be more than
60%.
-
Check12
Measure to prevent the rack
from toppling
Measure to prevent the rack from
toppling must be performed.
-