4
1.3
Installation Specifications
This section explains installation specification of each model.
1.3.1 Installation Specifications
TABLE 1.2 Installation Specifications
Items
Contents
Cisco C880 Server
(E7-8800 v2 CPU)
Cisco C880 Server
(E7-8800 v3 and
E7-8800 v4 CPUs)
Dimensions
[mm (in.)]
Width
445(17.52)
Depth (*1)
782(30.79)
Length
438(17.25) 10U
Mass [kg (lb)] (*2)
143(315)
Conditions for air
conditioner
Max. calorific
value
[kJ/h (BTU/h)]
Interruptible power source
21,600(20,500)
19,872(18,835)
High efficiency power supply (*13)
20,900(19,800)
19.224(18,221)
Displacement
[m3/min (ft
3
/min)]
(*3)
Recommended environmental
temperature
12(424)
Max.
28(989)
Temperature
and Humidity
conditions (*4)
At the time
of operation
Temperature [°C (°F)]]
(*5)
Humidity [%RH]
20 to 80
Max wet bulb
temperature [°C (°F)]]
29 (84.2)
Downtime
(*6)
Temperature [°C (°F)]]
0 to 50 (32 to 122)
Humidity [%RH]
8 to 80
Max wet bulb
temperature [°C (°F)]]
29 (84.2)
Noise [dB] (*7, *8)
60
Acoustic power level [B] (*8)
7.8
Permissible
Vibration [m/s
2
(gal)]
At the time of operation (Including
standby)
4.0 (400) (Composite seismic wave)
Downtime (*9)
10.0 (1000) (Composite seismic wave)
Permissible dust level [mg/m
3
]
0.15
Power supply
conditions
Input voltage and source resultant pulse number
200 to 240 VAC±10 %
1φ
Frequency and fluctuating Range
50/60 Hz + 2/-4%
Max power
consumption /
apparent power
At the time
of operation
Interruptible power
source (*13)
6.00 kW/6.19 kVA
5.52 kW/5.69kVA
High efficiency power
supply (*13)
5.81 kW/5.99 kVA
5.34 kW/5.51kVA
Downtime
0.084 kW
Power factor (*10)
0.95 or more
Inrush current [A] [Rush hours] (*11)
20 or less
Leak current [mA] (*12)
6.9 or less
*1: Dimensions without protrusions
*2: Numeric value when each optional device is mounted for maximum number of options.
However, rail for mounting rack (5.7kg) and cable type are not included.
Mass as per the installation configuration can be calculated using formula as shown below.
Device mass = 77 + (9.6 * A) + (2.5 * B) + (1.8 * C) + (3.3 * D) [kg]
A = Number of mounted SB (Minimum 1 to Maximum 4)
B= Number of mounted IOU (Minimum 1 to Maximum 4)
C= Number of mounted PSU (Minimum 2 to Maximum 6)
D= Number of mounted DU (Minimum 0 to Maximum 2)
*3: There are cases when device is overloaded or when abnormality is detected, FAN rotates at high-speed
even if recommended environmental temperature is used.